Data transmission interface

The instrument is not powered by the M-Bus interface and is equipped with galvanic isolation. In
a M-bus network with a maximum of 250 instruments, it is possible to perform 24 readouts a day
for each instrument. If fewer readouts are carried out and/or if the number of instruments installed
in the network (connected to the M-Bus system) is lower, any unused requests will be stored in
the instrument to be used when needed.

Note:

During communication via M-Bus, the selection button cannot be used.

The  M-Bus  protocol  complies  with  EN  13757-2,  EN  13757-3,  EN  1434-3  and  M-Bus
recommendation (Version 4.8, November 1997) – protocol IEC 870 parts 1, 2 and 4.

None of the meters can withstand a voltage greater than that permitted by the bus voltage (±
50 V). Use a level converter/master as an additional protective measure. 

The instruments can be installed in an M-Bus network by authorized and qualified personnel
only. 

Make  sure  that  the  structure  of  the  M-Bus  network  (length  and  diameter  of  the  cables)  is
compatible with the baud rate (2400 Baud) of the connected instruments. 

Recommended cable: telephone cable J-Y (ST) Y2 x 2 x 0,8 mm

2

.

LEAVE THIS MANUAL AS A REFERENCE GUIDE FOR THE USER

Safety information

CAUTION:
Failure  to  follow  these  instructions  may  result  in  personal  injury  or  damage  to
property. 

The device must be installed, commissioned and serviced by qualified technical
personnel.
Make sure that all connecting fittings are watertight.
Water temperatures higher than 50°C may cause severe burns. When installing,
commissioning and servicing the heat meter, take the necessary precautions so
that these temperatures will not be hazardous for people.

NB: Failure to observe these instructions for proper installation can impair operation and invalidate
warranty.

8

Summary of Contents for SENSONICAL ULTRA CAL19185M Series

Page 1: ...ly 3V lithium battery life 6 years Data reading via button activated LCD Data transmission interface M Bus Data memory E2 PROM Working ambient temperature 5 55 C Storage temperature and conditions 5 4...

Page 2: ...g the hydraulic section 6 The correct positioning of the hydraulic section of SENSONICAL ULTRA is on the return pipe attention must be paid to observe the correct direction of the flow The temperature...

Page 3: ...the ball valve TEE d Insert the probe and adjust its depth of immersion by means of the nipple e Tighten until it stops Commissioning the meter a Slowly open the shut off device check the hydraulic t...

Page 4: ...n be displayed are split into three levels and can be viewed using the selection button The standard mode without pressing the button shows the total heating and cooling energy consumption since the s...

Page 5: ...and pulse input meters 1 4 Total volume in m3 5 Instantaneous power in kW 6 Instantaneous flow rate in m3 h 7 Current date in format DD MM YY 8 Error Message alternating binary and hexadecimal display...

Page 6: ...g item 8 error message on the main level The instrument detects eight causes of error indicated by the number 1 in the eight digit code of the error message These causes of error can also occur togeth...

Page 7: ...nergy logs are not updated the new data are not saved No calculations are performed The flow rate and energy logs are not updated the new data are not saved No calculations are performed The flow rate...

Page 8: ...master as an additional protective measure The instruments can be installed in an M Bus network by authorized and qualified personnel only Make sure that the structure of the M Bus network length and...

Reviews: