background image

2

Installation

Preliminary recommendations

Comply with the 

following instructions

for installation and examine the 

installation diagram

.

Failure  to  observe  these  instructions  may  invalidate  warranty  and  correct  measurement  of  the
thermal energy.
1

Installing the SENSONICAL ULTRA series heat meter requires fitting the probe holder valve
code CAL19180 or the TEE code CAL19181 in the system on the flow pipe, observing all the
instructions on the relevant instruction sheet.

2

The flow temperature probe must be inserted in the probe holder valve or in the TEE so that
it reaches the centre of the pipe. Make sure that the probe 

does not touch

the bottom. The

immersion depth can be adjusted by means of the nipple.

3

The SENSONICAL ULTRA meter must be installed by technically qualified personnel.

4

The meter must be positioned on the pipe at a distance of more than 200 mm from motors,
switches and regulators and more than 50 mm from electrical cables in compliance with the
requirements of the EC directive on electromagnetic compatibility and to ensure interference-
free operation.

5

Flush the system before inserting the hydraulic section.

6

The 

correct  positioning

of  the  hydraulic  section  of  SENSONICAL  ULTRA  is  on  the  return

pipe; attention must be paid to 

observe the correct direction of the flow

. The temperature

probe not sealed to the template of the volume meter must 

necessarily

be inserted in the

pocket of the valve CAL19180 or TEE CAL19181 on the system flow line. Consider also that
the length of the flow probe cable is equal to 1.5 m and that it 

can be neither extended nor

shortened

;  if  it  is  too  long,  it  is  advisable  to  wind  it  and  secure  it  with  a  plastic  cable  tie.

Before and after the meter there must be 

shut-off ball valves

in case it needs to be replaced

or  inspected.  A  strainer  upstream  of  the  system  is  necessary  in  order  to  prevent  any
blockages.

7

We recommend installing a venting device: air bubbles can cause measurement errors.

8

Clean the instrument only if required using a cloth moistened with water.

9

When positioning, consider the risk of water dripping onto the electronic component of the
heat meter.

Contents of the pack

No.1 heat meter consisting of: detachable electronic unit, volume meter, two temperature probes.
All these parts are permanently connected to each other.
No.1 instruction sheet for installation.
No.1 sealing kit for flow probe and hydraulic section.
No.2 3/4’’ M tailpiece-nut fittings

Summary of Contents for SENSONICAL ULTRA CAL19185M Series

Page 1: ...ly 3V lithium battery life 6 years Data reading via button activated LCD Data transmission interface M Bus Data memory E2 PROM Working ambient temperature 5 55 C Storage temperature and conditions 5 4...

Page 2: ...g the hydraulic section 6 The correct positioning of the hydraulic section of SENSONICAL ULTRA is on the return pipe attention must be paid to observe the correct direction of the flow The temperature...

Page 3: ...the ball valve TEE d Insert the probe and adjust its depth of immersion by means of the nipple e Tighten until it stops Commissioning the meter a Slowly open the shut off device check the hydraulic t...

Page 4: ...n be displayed are split into three levels and can be viewed using the selection button The standard mode without pressing the button shows the total heating and cooling energy consumption since the s...

Page 5: ...and pulse input meters 1 4 Total volume in m3 5 Instantaneous power in kW 6 Instantaneous flow rate in m3 h 7 Current date in format DD MM YY 8 Error Message alternating binary and hexadecimal display...

Page 6: ...g item 8 error message on the main level The instrument detects eight causes of error indicated by the number 1 in the eight digit code of the error message These causes of error can also occur togeth...

Page 7: ...nergy logs are not updated the new data are not saved No calculations are performed The flow rate and energy logs are not updated the new data are not saved No calculations are performed The flow rate...

Page 8: ...master as an additional protective measure The instruments can be installed in an M Bus network by authorized and qualified personnel only Make sure that the structure of the M Bus network length and...

Reviews: