background image

12

Heating function

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

Text (°C)

flo

w

 (

°C

)

MIN

5

0

-5

-15

MAX

10

-10

20

15

25

30

-20

k = 3.0

k = 2.5

k = 2.0

k = 1.5

k = 1.0

k = 0.5

k = 0.0

MAX is the set temperature value
MIN is 45°C for HIGH temp. HIUs, 25°C for LOW temp. ones.

HIU setting at HIGH/LOW temperature

The  HIU  is  set  at  LOW  temperature  by  default  (underfloor  heating,
parameter t00 = 1). To change this setting and supply a system with
high  temperature  terminals  go  to  the  technical  menu  (see  page  11)
and set parameter t00 to 0.

DEFAULT SETTING: set point regulation
(technical parameter t01 = 0)

When  heating  cycle  activation  is  requested  by  the  room  thermostat,
the circulation pump is powered while the modulating valve is opened
gradually until the set point temperature is reached.
The circulation pump is stopped and the modulating valve is closed at
the end of the heating cycle. The heating cycle ON condition is indicated
by the blinking

symbol.

OPTIONAL  SETTING:  primary  return  temperature  limit
(technical parameter t01 = 1)

When  heating  cycle  activation  is  requested  by  the  room  thermostat,
the circulation pump is powered while the modulating valve is opened
gradually  until  the  set  point  temperature  is  reached,  if  the  return
temperature is lower than or equal to the set limit value. In case this
condition is not met, the flow temperature is reduced (by a maximum
of  15°C  for  HIU  in  HIGH  temperature,  and  maximum  3°C  if  in  LOW
temperature),  in  order  to  bring  return  temperature  within  the  limit
values. When the flow temperature must be reduced in order to limit
return, the 

icon appears on the display.

Heating flow/ primary return limit temperature setting

To set the flow temperature press the <SET> key until the symbol in
the red circle appears; for the return temperature limit press the key
until the symbols in the green circle are displayed. Use the <R> knob
to change the value (*).
The flow temperature range is:
25–45°C    for heat interface units in LOW temperature
45–75°C    for heat interface units in HIGH temperature
The primary return limit temperature range is:
15–42°C    for heat interface units in LOW temperature
30–70°C    for heat interface units in HIGH temperature

OPTIONAL  SETTING:  modulating  temperature  regulation  with
compensated set point (technical parameter t01= 2)

When  the  function  is  enabled,  the  flow  temperature  is  modified
(±  10°C  with  respect  to  the  set  point  for  HIU  in  HIGH  temperature, 
± 3°C if in LOW temperature) according to the temperature detected
by the return probe in order to maintain this latter temperature value
constant.  This  keeps  the  actual  thermal  output  of  the  slab  under
control, and consequently also the ambient thermal load. The thermal
response time of the system is thus minimised.
This  feature  should  not  be  used  in  combination  with  thermostatic
radiator valves.

When the function is enabled the display shows the symbol 

.

OPTIONAL  SETTING:  weather  compensation  (technical
parameter t01 = 3)

When  the  function  is  enabled,  the  flow  temperature  is  calculated
based on the temperature detected by the outside probe (optional), in
accordance  with  the  curve  shown  below.  The  “k”  coefficient  can  be
changed by pressing <SET> button until the related setting appears.

The display shows the symbol 

.

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

   

 

 

   

 

 

 

 

 

 

(*) if these set points cannot be changed you must set parameter t07
to  value  0  in  the  technical  menu  (see  “access  to  technical  menu”
below).  Parameter  t07  =  1  “freezes”  the  operating  set  points  to
prevent inadvertent modifications by the user.

 

 

 

     

 

 

 

 

 

 

   

 

 

   

 

 

 

 

Summary of Contents for SATK32 Series

Page 1: ...de 10 Commissioning 9 Electrical installation 8 Hydraulic installation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions P...

Page 2: ...k must be carried out on the device cut off the electric supply first Do not use devices with automatic or time reset or which may be reset accidentally 4 Use suitable automatic protection devices in...

Page 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Page 4: ...be 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Connection for M10x1 heat m...

Page 5: ...kflow preventer code 572120 proceed as follows remove the nuts shown in the figure with letter A Hydraulic installation Preliminary operations installation without template After having established th...

Page 6: ...tem in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In...

Page 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Page 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Page 9: ...necessary restore the pre charge value shown in the technical specifications Filling the user system SATK32 series HIU can be fitted with a charging unit equipped with a backflow preventer F check va...

Page 10: ...ng modes OFF DHW only summer mode Heating DHW winter mode Heating only Selecting set points current time and comfort function Press the set key repeatedly to set the current time set point temperature...

Page 11: ...arious parameters which can then be edited pressing and rotating knob R Technical parameter t00 Primary limit set return temperature in heating mode Primary limit set return temperature in DHW mode Co...

Page 12: ...ng To set the flow temperature press the SET key until the symbol in the red circle appears for the return temperature limit press the key until the symbols in the green circle are displayed Use the R...

Page 13: ...7 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DHW plate heat exchanger or management of DHW recircul...

Page 14: ...posed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between th...

Page 15: ...es a sequence of LEDs showing the instantaneous power consumption 1 yellow LED lit power between 0 and 25 of Pmax 2 yellow LEDs lit power between 25 and 50 of Pmax 3 yellow LEDs lit power between 50 a...

Page 16: ...must be set to 1 2 4 7 This value t05 7 is set by default example 2 Distinction of consumption for DHW production from total consumption in combination with heat meter equipped with dedicated function...

Page 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Page 18: ...nd disabled Any requests to run cycles not associated to the previous one will continue to run normally Heating flow probe fault Error code 5 Domestic hot water probe fault Error code 6 Return probe f...

Page 19: ...o be interfaced with controllers managing the heating and DHW production services by means of pre paid type logic The HIU interprets an open contact as credit available Closing the contact disables th...

Page 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Page 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Page 22: ...r partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced DHW temperature probe cable inverted with heating probe rest...

Page 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not work...

Page 24: ...s external sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside t...

Reviews: