Check valves

In order to prevent undersirable backsiphonage, separate check valves should be installed in systems 
with code “521 A” model thermostatic mixing valves (these models do not contain integral check valves 
in the hot and cold inlet ports). As a convenience for easier installations, the Caleffi code “521 AC” 
model series thermostatic mixing valves include integral check valves in the hot and cold inlet ports. 
 

NOTE TO INSTALLER: DO NOT TEST FIT OR INSTALL CHECK VALVES BEFORE SOLDERING. IF 
INSTALLED, REMOVAL WILL REQUIRE DAMAGING THE CHECK VALVE AND IT WILL NO LONGER 
BE USABLE.

The diagram below shows the order in which everything goes together. Note that the check valves 
are installed on the hot and cold inlets, the mixed outlet does not require a check valve. Note that the 
O-ring is installed on to the groove of the check valve.

After soldering the tailpieces into place, slide in the check valve into the tailpiece with o-ring going in 
first. It will click into place and then the screen will fit into the groove of the tailpiece with the domed 
end facing the mixing valve. Once the check valve and screen is installed, use the sealing washer 
between the tailpiece and mixing valve body to create a seal and tighten down the union nut.

Commissioning 

The special purpose of the thermostatic mixing valve must be commissioned in accordance with 
current standards by qualified personnel using temperature measuring equipment.  Caleffi codes 
521419A,  521519A, and 521619A with integral outlet port temperature gauges provide a time-saving 
temperature setting process to get close to the desired temperture. Use of a digital thermometer is 
recommended for determining the final setting of the mixed water temperature.
NOTE: Gauge adapters with 2” diameter, 20-210ºF scale, code NA10328 (1/2” sweat),  NA10056 
(3/4” sweat) or NA10058 (1” sweat) can be separately purchased and field installed to the Caleffi 
MixCal series 521 models sold without the integral gauge adapters.
After installation, the valve must be tested and commisioned in accordance with instructions given 
below, taking into account current applicable standards.
1)  Ensure that the system is clean and free from dirt or debris before commissioning the thermostatic 
mixer.
2)  It is recommended that the temperature is set using a suitable calibrated digital thermometer. 
The valve must be commissioned by measuring the temperature of the mixed water emerging at the 
point of use.
3)  The maximum outlet temperature from the valve must be set taking account of the fluctuations 
due to simultaneous use. It is essential for these conditions to be stabilised before commissioning.
4)  Adjust the temperature using the adjusting knob on the valve. For safety reasons. it is advisable to 
limit the maximum mixed water temperature to 120ºF in domestic hot water systems. 

4

1

3

1

4

6

2
3

VALVE BODY

UNION NUT, Quantity 3 per valve

UNION WASHER, Quantity 3 per valve

INLET PORT MALE TAILPIECE

WITH INTEGRAL CHECK VALVE

Quantity 2 per valve

INLET PORT CONIC FILTER,

Quantity 2 per valve

7

OUTLET PORT TAILPIECE,

Quantity 1 per valve

5

CHECK VALVE O-RING

2 3 6

6

7

4

2

5

5

(SWEAT TAILPIECE)

6

Summary of Contents for MixCal 521 Series

Page 1: ...ontent Reduction of Lead in Drinking Water Act California Health and Safety Code 116875 S 3874 Reduction of Lead in Drinking Water Act certified by ICC ES file PMG 1360 Function The Caleffi MixCal three way thermostatic mixing valve is used in systems producing domestic hot water or in hydronic and radiant heating systems With the unique mixing chamber design MixCal produces very stable mixed wate...

Page 2: ...ntenance of the MixCal thermostatic mixing valve take the necessary precautions to ensure that such temperatures do not endanger people CAUTION To prevent any damage which will cause the electronic mixing valve to not operate correctly treat highly aggressive water before entering the electronic mixing valve Be sure water hardness is less than 10 grains CAUTION If installed in an ASSE 1017 applica...

Page 3: ...rdepression termostaticoregolabile n estpasinstallé mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer que tous les raccordements sont étanches ATTENTION Les températures de l eau supérieure à 100 F 38 C peut être dangereux Au cours de l installation mise en serv...

Page 4: ... hot or cold water for other uses or variations in the incoming temperature the thermostatic mixing valve automatically regulates the water flow to obtain the required temperature COLD HOT MIX Inlet port check valve detail for 521 AC models Flow curve Flow should never exceed standards for pipe size and materials Kv 2 6 0 1 10 0 023 0 23 0 046 0 069 0 02 0 05 0 2 0 5 0 115 2 3 0 46 0 69 1 15 20 50...

Page 5: ...the system must be inspected to ensure that it s operating conditions are within the range of the thermostatic mixing valve checking for example the supply temperature supply pressure etc Systems where the Caleffi MixCal series 521 thermostatic mixing valve is to be installed must be drained and cleaned out to remove any dirt or debris which may have accumulated during installation Failure to remo...

Page 6: ...19A and 521619A with integral outlet port temperature gauges provide a time saving temperature setting process to get close to the desired temperture Use of a digital thermometer is recommended for determining the final setting of the mixed water temperature NOTE Gauge adapters with 2 diameter 20 210ºF scale code NA10328 1 2 sweat NA10056 3 4 sweat or NA10058 1 sweat can be separately purchased an...

Page 7: ... HOT COLD MIX BOILER SUPPLY MIX 3 2 4 MIX 3 2 4 Safety relief valve Check valve Isolation valve Expansion vessel Filter Pump WATER HEATER WATER HEATER CALEFFI CALEFFI CALEFFI CALEFFI 10 0 8 6 4 2 10 0 8 6 4 2 CALEFFI CALEFFI 10 0 8 6 4 2 10 0 8 6 4 2 10 0 8 6 4 2 10 0 8 6 4 2 Domestic hot water system without recirculation Domestic hot water system with recirculation CALEFFI 3 2 4 COLD HOT HOT RED...

Page 8: ...94A NA20669 Sweat 59834A NA20669C 59906A NA20666 Press NA16266 NA20667 PEX crimp F61008 F0000521 NA20667A NA10486 Replacement parts Replacement body Meets requirements of NSF ANSI 372 2011 Certified to ASSE 1017 CSA B125 3 Low lead by ICC ES file PMG 1360 ASSE 1017 521101A 1 male union thread Point of distribution mixed temperature gauge adaptor fits MixCal 521 series mixing valves Threaded union ...

Page 9: ...gnificantly in comparison with the previous test the details given in the installation and commissioning sections should be checked and maintenance conducted The following should be checked regularly to ensure that the optimum performance levels of the valve are maintained Check every 12 months at least or more often if necessary 1 Check and clean the system filters 2 Check that any check valves p...

Page 10: ...lets of the valve c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient water supplies b Fluctuations in the supply pressures temperatures c Adverse effect created by other draw off points on the system Stabilize inlet supply condi tions No flow of water from the valve a In line filers blocked b Insufficie...

Page 11: ...11 this page left blank intentionally ...

Page 12: ...Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 12 1 17 12 ...

Reviews: