17
Presence of Recirculation Probe
BV
34
1 = Presence of Rec probe
Anticlog
BV
35
1 = Anticlog
Legal Hour
AV
36
bit 2:0 bit 3:1 = Disabled
bit 2:1 bit 3:0 = EUR
bit 2:0 bit 3:1 = USA
bit 2:1 bit 3:1 = Custom
International System of Unit
BV
37
0 = °C , 1 = °F
LED Display Enable
BV
38
1 = LED display enable
Shock Activation
BV
39
0 = Shock Activation
Pin-code Reset
BV
40
1 = Pin-code Reset
Disinfection Reset
BV
41
2 = Disinfection Reset
Alarm Reset
BV
42
3 = Alarm Reset
Historical Data
BV
43
4 = Historical Data
Time Motor (Time to move actuator
from close to open position)
AV
44
8...320 (sec)
Time Play (Delay of time in move-
ment of actuator while changing
direction)
AV
45
1...255 (sec)
Start Sunday Legal Hour
*
AV
46
-3, -2, -1, 1, 2, 3
Start Month Legal Hour
AV
47
1...12
End Sunday Legal Hour
*
AV
48
-3, -2, -1, 1, 2, 3
End Month Legal Hour
AV
49
1...12
*
It’s possible to choose the day of the hour change by setting the parameter #36 (Legal Hour) to “Custom”:
set:
-1
for the last Sunday of the month;
set:
-2
for the second to last Sunday of the month;
set:
-3
for the third last Sunday of the month;
set:
1
for the first Sunday of the month;
set:
2
for the second Sunday of the month;
set:
3
for the third Sunday of the month.