Installation

The 573 Series FlowShield DuC-AV backflow preventer with atmospheric vent must be installed 
in accordance with the diagrams contained in this instruction manual taking into account all the 
applicable Codes and Regulations.

Before installing, the system must be thoroughly flushed to remove impurities or any debris which 
may have accumulated during installation. Failure to remove dirt or debris may affect performance 
and the manufacturer’s guarantee.

The 573 Series FlowShield DuC-AV backflow preventer must be installed preferably horizontally 
and following the flow direction indicated by the arrow on the valve body.

It also must be installed with one isolating valve and a strainer upstream and one isolating valve 
downstream.

The 573 Series FlowShield DuC-AV backflow preventer must be installed in an accessible location 
to facilitate testing and servicing.

It must be installed with the vent port connected via an air gap to a discharge line, in accordance 
with the plumbing code requirements and keeping a minumum distance of 12” from the floor. 

Do not install where the discharge can could cause damage.

If field testing is required by code, it must be installed in accordance with the relevant diagram in 
this instruction manual.

NOTE: 

When installing the 573 series FlowShield DuC-AV with sweat tailpieces, sweat the tailpiece to the 
pipe before installing the body which includes an embedded o-ring. 

5

Summary of Contents for 573 Series

Page 1: ...ric vent size 1 2 3 4 NPT female threaded connection with union size 1 2 sweat connection with union size 1 2 press connection with union Technical specifications Connections 1 2 3 4 NPT female with u...

Page 2: ...echanically over stressed Over time this could cause breakages with consequent water losses which in turn could cause harm to property and or people Caleffi shall not be liable for damages resulting f...

Page 3: ...ci pourrait causer des ruptures avec pour cons quence des pertes en eau qui leur tour peuvent causer des dommages la peopri t et ou les gens Caleffi ne pourra etre tenue responsable des dommages resul...

Page 4: ...4 Flow rate graph 10 2 5 10 5 20 50 Dp psi G l min gpm 20 10 5 psi bar 20 1 0 5 10 2 5 15 1 0 52 0 3 Cv 0 7 VENT p psi p psi bar G l min gpm...

Page 5: ...arrow on the valve body It also must be installed with one isolating valve and a strainer upstream and one isolating valve downstream The 573 Series FlowShield DuC AV backflow preventer must be instal...

Page 6: ...s 1 2 S N VENT Heating system application BACKFL OW PRE V Series 573 Sizes 1 2 S N VENT Field testing installation SUPPLY Inlet test valve Upstream shut off valve Y strainer Upstream test valve 573 se...

Page 7: ...ightness of the internal second check valve When backpressure is applied to the downstream side of the valve the internal second check valve must close back drip tight on its seat a Close shutoff valv...

Page 8: ...8 NOTES Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 09 2023 For Technical Support call 1 414 338 6338 or email techsupport us caleffi com...

Reviews: