Product range

521201A  SinkMixer Under sink thermostatic mixing valve, 
521201AP includes plug for cold water outlet...........................................size 

3

/

8

” compression 

SinkMixer™ Under Sink Thermostatic Mixing Valve

Technical specifications

Materials:

 

 

- Valve body, regulating spindle, spring holder and cold inlet union nut:

 

 

Low-lead brass (<0.25% lead content)

 

- Internal shutter: 

Polysulfone

 

- Hot inlet strainer:                                                               AISI 304 stainless steel 

 

- Spring: 

AISI 302 stainless steel

 

- Seals: 

Peroxide-cured EPDM

 

- Cover: 

ABS white

 

- Mounting bracket and adjustment key: 

Polyamide Nylon

Temperature adjustment range: 

95–120°F (35–50°C)

Temperature set:  

must be commissioned on site to achieve desired temperature

Temperature stability: 

±3°F (±2°C)

Cold inlet temperature: 

Minimum 39°F (4°C); Maximum 85°F (29°C)

Hot inlet temperature: 

Minimum 120°F (49°C); Maximum 195°F (90°C)

Factory setting: 

113°F (45°C)

Maximum operating differential pressure: 

Static: 150 psi (10 bar); Dynamic: 70 psi (5 bar)

Minimum operating differential pressure (dynamic): 

1.5 psi (0.1 bar)

Maximum unbalanced dynamic supply (hot/cold or cold/hot):   

 

 

2:1

Minimum temperature differential between hot water inlet

   and mixed water outlet to ensure thermal shutoff function: 

18°F (10°C)

Minimum temperature differential between mixed water outlet

   and cold water inlet to ensure stable operation: 

9°F (5°C)

Minimum flow rate for optimum operation: 

0.35 gpm (1.3 l/min)

Maximum flow rate for optimum operation: 

2.3 gpm (8.5 l.min)

Certifications:     

1. ASSE 1070/CSA B125.3-2012, certified by ICC-ES, file PMG-1358.

2. NSF/ANSI 372-2011, Drinking Water Systems Components-Lead Content Reduction of Lead in 

Drinking Water, California Health and Safety Code 116875 S.3874, Reduction of Lead in Drinking 

Water Act, certified by ICC-ES, file PMG-1360.

3. Complies with codes IPC, IRC, UPC and NPC.

1

© Copyright 2020 Caleffi

code 521201A,AP 

H0007288.01

www.caleffi.com

ASSE 1070

INSTALLATION AND COMMISSIONING MANUAL

Function

The Caleffi SinkMixer™ thermostatic mixing valve is used in under sink 

and under counter applications where the user must be protected 

from the danger of scalding caused by hot water. The Caleffi SinkMixer 

provides water at a safe and usable temperature in situations where 

the control of the temperature of the water discharging from a terminal 

fitting is of the utmost importance, i.e. within hospitals, schools, 

nursing homes, etc. The valve is designed to prevent the flow of water 

discharging from the mixed water outlet in the event of the failure of 

hot or cold supply. It is compact for easy installation and includes a 

cold water outlet to the fixture eliminating the need for additional piping 

and tee for standard three-port mixing valves. For single-pipe fixtures 

(tempered water only), code 521201AP includes a plug for the valve 

cold outlet port. It has integral check valves on the hot and cold inlets 

and is certified to Low Lead Plumbing Law by ICC-ES, ASSE 1070 listed 

(temperature cannot exceed 120°F).

Summary of Contents for 521201AP

Page 1: ...um flow rate for optimum operation 2 3 gpm 8 5 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1358 2 NSF ANSI 372 2011 Drinking Water Systems Components Lead Content Red...

Page 2: ...t such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Page 3: ...tpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Page 4: ...water in such a way as to maintain constant set temperature of the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expands causin...

Page 5: ...and under counter applications in accordance with installation rules and indications specified in ASSE 1070 standards The system must be sized taking into account the current legislation with regard...

Page 6: ...ked at any need Hand changes are forbidden Questodocumentonon daritenersiimpegnativo Ciriserviamoildirittodimodificareinostriprodotti diapportaremiglioramentitecniciedisvilupparliulteriormente Attenzi...

Page 7: ...or associated fittings It is essential that when the installation is designed and or installed all current legislation is noted e g the maximum distance from the outlet of the valve to any terminal fi...

Page 8: ...Installation diagram COLD HOT 8 Point of use 521201A 521201AP...

Page 9: ...to simultaneous demand 5 Once the supply temperatures are stabilized and the normal operating conditions are established the valve can be commissioned The temperature setting can be adjusted by with...

Page 10: ...D C O L D H O T M I X Remove 1 4 hex key from mounting bracket Remove white cap Adjust temperature setting with 1 4 hex key After adjustment lock the temperature with locking nut Replace cap and store...

Page 11: ...e following steps are checked to maintain optimum valve performance Use the folllowing recommended procedure 1 On the Caleffi SinkMixer valves the inlet strainers on both the hot and cold water inlet...

Page 12: ...Starvation of the water supplies at the valve inlets c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient...