background image

5

Installation

Indications,

 functions and options

Operation and function

en

2  Installation

2.1  Mounting

WARNING!

Electric shock!
Upon opening the housing, live parts are exposed!

 

Î

Always disconnect the device from power supply 
before opening the housing!

Note:
Strong electromagnetic fields can impair the function of the controller.

 

Î

Make sure the controller as well as the system are not exposed to 
strong electromagnetic fields.

The unit must only be located in dry interior rooms. 
The controller must additionally be supplied from a double pole switch with contact 
gap of at least 3 mm.
Please pay attention to separate routing of sensor cables and mains cables.
In order to mount the device to the wall, carry out the following steps:

 

Î

Unscrew the crosshead screw from the cover and remove it along with the 
cover from the housing.

 

Î

Mark the upper fastening point on the wall. Drill and fasten the enclosed wall 
plug and screw leaving the head protruding.

 

Î

Hang the housing from the upper fastening point and mark the lower fastening 
point (centres 130 mm).

 

Î

Insert lower wall plug.

 

Î

Fasten the housing to the wall with the lower fastening screw and tighten.

 

Î

Carry out the electrical wiring in accordance with the terminal allocation (see 
chapter 2.2).

 

Î

Put the cover on the housing.

 

Î

Attach with the fastening screw.

2.2  Electrical connection

WARNING!

Electric shock!
Upon opening the housing, live parts are exposed!

 

Î

Always disconnect the device from power supply 
before opening the housing!

ATTENTION!

ESD damage!
Electrostatic discharge can lead to damage to electronic com-
ponents!

 

Î

Take care to discharge properly before touching the 
inside of the device! To do so, touch a grounded sur-
face such as a radiator or tap!

Note:
Connecting the device to the power supply must always be the last step 
of the installation!

The controller is supplied with power via a mains cable. The power supply of the 
device must be 100 … 240 V~ (50 … 60 Hz).
The controller is equipped with 4 relays in total, to which loads such as pumps, 
valves, etc. can be connected:
•  Relays 1 … 3 are semiconductor relays: 

Conductor  R1 … R3
Neutral conductor N
Protective conductor 

•  Relay 4 is a potential-free extra-low voltage relay
Depending on the product version, mains cables and sensor cables are already con-
nected to the device. If that is not the case, please proceed as follows:
Connect the temperature sensors (S1 to S3) to the following terminals with 
either polarity:
S1  = Sensor 1 (outdoor temperature sensor)
S2  = Sensor 2 (heating circuit flow)
S3  = Sensor 3 (e. g. return sensor)
Connect the remote control (if used in the system selected) to the S3 / RTA12 
input with either polarity.
Connect the room thermostat to the TA input with either polarity.
Connect the dew point switch (if used in the system selected) to the S5 / TS10 
input with either polarity.

Summary of Contents for 161010

Page 1: ...nce from this unit Please keep this manual safe Manual en Heating controller Manual for the specialised craftsman Installation Operation Troubleshooting Digital controller with system representation 1...

Page 2: ...tem are not exposed to strong electromagnetic fields Subject to technical change Errors excepted Target group These instructions are exclusively addressed to authorised skilled personnel Only qualifie...

Page 3: ...allation 5 2 1 Mounting 5 2 2 Electrical connection 5 3 Operation and function 6 3 1 Buttons and adjustment dial 6 3 2 Adjustment values and user code 6 3 3 Control LED 7 4 Systems 7 5 Indications fun...

Page 4: ...acity 4 A 240V Power supply 100 240V 50 60 Hz Supply connection typeY attachment Power consumption 1 W Mode of operation type 1 B C Y action Rated impulse voltage 2 5 kV Data interface VBus VBus curre...

Page 5: ...ning screw 2 2 Electrical connection WARNING Electric shock Upon opening the housing live parts are exposed Always disconnect the device from power supply before opening the housing ATTENTION ESD dama...

Page 6: ...ng the device to the mains Note The connection depends on the system layout selected see page 7 The auxiliary terminals can be used instead of R4 as the mixer switch for the heat generator if a voltag...

Page 7: ...ipped with a non adjustable safety shutdown function If the temperature at S2 reaches or exceeds 90 C the mixer closes The warning symbol appears on the screen and the Lightwheel flashes yellow If the...

Page 8: ...pressure monitoring tMixer 75 s 30 240 s Mixer runtime Corr tMixer 90 s 5 300 s Surplus mixer runtime when the mixer is closing tPLAY 4 s 1 15 s Mixer control time for change of flow direction Block...

Page 9: ...a switch for remotely controlling the heating cooling mode Contact open cooling mode Contact closed heating mode If the Condensation option is activated the controller monitors a dew point switch If t...

Page 10: ...lock prot Yes Yes No Blocking protection option PWM Heating Heating Solar PWM profile PWM A Slab drying Slab drying submenu TStart 20 C 10 C 30 C Slab drying start temperature TMax 45 C 20 C 60 C Slab...

Page 11: ...e in system 2 The room thermostat demands cold the outdoor temperature is indicated 5 2 Display values In order to access the display values from the home screen briefly press the right button 5 3 War...

Page 12: ...in Minimum temperature heating circuit option 5 4 Con guration In order to access the adjustment values from the home screen press the right button for approx 3 s and enter the user code see page 6 Ts...

Page 13: ...heating circuit TMax Maximum temperature heating circuit option TMax Maximum temperature heating circuit tLimit Time for which the calculated set flow temperature is to be used Remote control Remote c...

Page 14: ...ing tPLAY Mixer control time for change of flow direction Block prot Blocking protection option PWM PWM profile selection Chiller on Cooling demand on if the dew point switch detects condensation only...

Page 15: ...on and function en Slab drying Slab drying submenu TStart Start temperature TMax Holding temperature Rise Rise value Rise time Rise duration tBacking TMax holding time Start Activation Deactivation of...

Page 16: ...nsor Min press Max press Minimum and maximum pressure The balance values can be set back to zero In order to reset a value proceed as follows Select the desired value and press the right button Does t...

Page 17: ...tomatic operation Off Relay off Man 2 3 Manual mode of the mixer For control and service work the operating mode of the mixer can be manually adjusted Mixer open Relay 2 on Relay 3 off Auto Relays 2 a...

Page 18: ...plication example 6 1 2 8 9 10 11 12 13 4 5 1 Outdoor temperature sensor 2 Heating circuit flow 3 Return sensor optional 4 Room thermostat 5 Dew point switch optional 6 Boiler demand when voltage 30V...

Page 19: ...1290 15 1058 80 1309 20 1078 85 1328 25 1097 90 1347 30 1117 95 1366 35 1136 100 1385 40 1155 105 1404 45 1175 110 1423 50 1194 115 1442 Short circuit or line break Disconnected temperature sensors ca...

Page 20: ...Distributed by Distributed by Caleffi S p A S R 229 no 25 IT 28010 Fontaneto d Agogna NO All contents of this document are protected by copyright...

Reviews: