CAL
-SERIES
6
4.0
SPECIFICATIONS:
GENERAL SPECIFICATIONS
Rating:
(Input: Natural and Propane Gas)
In Canada: 0-4500' (1372 m) In USA: 0-2000' (610 m) - De-rate Above 2000' (610 m) (see pg 48)
MODEL
BURNER INPUT BTU/hr
TUBE LENGTH
MIN
MAX
MIN
MAX
CAL-35A
n/a
35,000
10' (3 m)
20’ (6.1 m)
CAL-35AHL
17,500
35,000
10' (3 m)
20’ (6.1 m)
CAL-35AM
17,500
35,000
10' (3 m)
20’ (6.1 m)
CAL-40A
N/A
40,000
10' (3 m)
20’ (6.1 m)
CAL-40AHL
20,000
40,000
10' (3 m)
20’ (6.1 m)
CAL-40AM
20,000
40,000
10' (3 m)
20’ (6.1 m)
CAL-50A
N/A
50,000
15' (4.2 m)
20’ (6.1 m)
CAL-50AHL
25,000
50,000
15' (4.2 m)
20’ (6.1 m)
CAL-50AM
25,000
50,000
15' (4.2 m)
20’ (6.1 m)
CAL-75A
N/A
75,000
20' (6.1 m)
30’ (9.14 m)
CAL-75AHL
37,500
75,000
20' (6.1 m)
30’ (9.14 m)
CAL-75AM
37,500
75,000
20' (6.1 m)
30’ (9.14 m)
CAL-80A
n/a
40,000
80,000
20' (6.1 m)
40’ (12.2m)
CAL-80AHL
40,000
80,000
20' (6.1 m)
40’ (12.2m)
CAL-80AM
40,000
80,000
20' (6.1 m)
40’ (12.2m)
CAL-100A
n/a
100,000
30’ (9.14 m)
50’ (15.2m)
CAL-100AHL
50,000
100,000
30’ (9.14 m)
50’ (15.2m)
CAL-100AM
50,000
100,000
30’ (9.14 m)
50’ (15.2m)
CAL-125A
n/a
125,000
40’ (12.2m)
50’ (15.2m)
CAL-125AHL
62,500
125,000
40’ (12.2m)
50’ (15.2m)
CAL-125AM
62,500
125,000
40’ (12.2m)
50’ (15.2m)
GAS PRESSURE at MANIFOLD:
SINGLE INPUT:
VARIABLE INPUT:
Natural Gas:
3.5" (8.89 cm) W.C.
Lo: 1.5" (3.8 cm) W.C.
Hi 3.5" (8.89 cm) W.C.
Propane Gas:
10.5" (26.67 cm) W.C.
Lo: 5.5" (13.97 cm) W.C.
Hi: 10.5" (26.67 cm) W.C.
Gas Connection
Size:
0.5" (1.27 cm) N.P.T.
GAS INLET PRESSURE:
GAS:
MINIMUM:
MAXIMUM:
Natural
4.5" (11.43 cm) W.C.
14.0" (35.56 cm) W.C.
Propane
11.5" (29.21 cm) W.C.
14.0" (35.56 cm) W.C.
ELECTRICAL RATING:
DSI Ignition, 120v. 60hz, 1 Amps, Appliance, 3 prong plug connection, 24-volt low voltage thermostat.