FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 18/57
IV.3.
TEMPERATURE SENSOR WIRING (Except SEASON)
Temperature sensors are connected on the controller
o
SSG : Supply temperature sensor on Agnd(30) and AI1(31)
o
SEG : Outdoor temperature sensor on Agnd(30) et AI2(32)
o
SRG : Extract temperature sensor on Agnd(33) et AI3 (34)
IV.4.
TERMINAL BLOCKS OF FREETIME
®
(Except SEASON)
Désignation
Bornes
Raccordement
ADP (shunted if not
used)
1-2
Connect on fire emergency stop (free voltage NC contact)
DAD (shunted if
not used)
3-4
Connect on DAD (smoke detector) default contact (NC)
THA/THS (shunted
if not used)
5-6
Connect to NC free voltage contact of THA (
PREMIUM BC - CO
)
Or
Connect to NC free voltage contact of THS (
PREMIUM BE
)
ED-TOUCH
7-8 + A*-B*
(port2)
Connect to remote touch screen display
MF PV
9-10
Connect to NO free voltage contact of reduced Speed extended operation
MF GV
11-12
Connect to NO free voltage contact of normal Speed extended operation
ARR EXT
13-14
Connect to NO free voltage contact of external stop