FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 33/57
V.4. Operator parameters modification ( password 3333 required)
V.4.a. Dates and hours clocks setting
V.4.a.1.
Date and hour of the CORRIGO controller [(1) chapter V.3.d]
Access : Hour Date setting
Date and hour of the regulator are set by defaut in the CORRIGO controller. Summer/Winter time is automatically managed.
V.4.a.2.
Hour programmation of the functionning system [(2) (3) chapter V.3.d]
Access :
o
Timer normal speed : Time settings / normal speed programm
o
Timer reduced speed : Time settings / slow speed programm
System is set to work in normal speed (HS-1/1) 07:00 - 22:00 in slow speed (LS-1/2) 22:00 - 06:00 except DIVA / LOBBY /
QUATTRO versions which work in slow speed (LS-1/2)
As indicated in arborescence you also have the possibility to modify Monday to Friday periods by pressing the right button
when you are on the Monday screen
Nota : if slow speed (LS-1/2) and normal speed (HS-1/1) are activated in the same time window, unit works in high speed
Operation exceptions:
DIVA
®
/QUATTRO
®
: For CO2 regulation do not activate any normal speed time window (GV-1/1)
LOBBY: Only slow speed clock (LS-1/2) must be activated
NIGHT COOLING: Only works if unit is in slow speed (LS-1/1) between 00:00 and 07:00.AM (Example: If
unit is in (LS-1/2) between 02:00 and 06:00 and in (HS-1/1) the rest of the time. Then NIGHT COOLING is allowed to work
only from 02:00 to 06:00 AM)
V.4.a.3.
Vacation time [(4) chapter V.3.d] (password 3333 required)
Access : Hour settings / holidays
System is set with no vacation time. If you need to reduce functionnement time during vacation time, set the functionning time
window as indicated in chapter V.3.4), and set the vacation days.
V.4.b. Speed /pressure modification in LS and HS
V.4.b.1.
STANDARD (ECO) / DIVA [(5) chapter V.3.c]
Access : ventilation Regul / Frequency control VAS 1/1 and 1/2 or frequency control VAR 1/1 et 1/2
You can modify the rotation speed of the unit in PV-1/2 (slow speed) and in HS-1/1 (normal speed) for each fan to set the
airflows.
o
To set the initial airflow (GV-1/1), force the system in normal speed with available terminals « Forced start HS »
(bridge between 11 and 12 terminals).
o
To set the initial airflow LS, force the system in slow speed with available terminals « Forced start LS » (bridge
between 9 and 10 terminals).
V.4.b.2.
LOBBY [(5) chapter V.3.c]
Access : ventilation Regul / Pressure control VAS 1/2 or Pressure control VAR 1/2
You can modify the constant pressure of the unit for each fan to set the airflows.
o
To set the initial airflows LS, force the le system in normal speed with available terminals « Forced start LS » »
(bridge between 9 and 10 terminals).
V.4.b.3.
MAC2
®
/QUATTRO
®
[(5) chapitre V.3.c]
Access : ventilation Regul / Airflow control VAS 1/1 and 1/2 or Airflow control VAR 1/1 and 1/2
You can modify the rotation speed of the unit in PV-1/2 (slow speed) and in HS-1/1 (normal speed) for each fan to set the
airflows.
o
To set the initial airflow (GV-1/1), force the system in normal speed with available terminals « Forced start HS »
(bridge between 11 and 12 terminals).
o
To set the initial airflow LS, force the system in slow speed with available terminals « Forced start LS » (bridge
between 9 and 10 terminals).