CALogix
installation
sheet
Page
6
of
6
Specification
PID MODULE :
THERMOCOUPLE
– 9 Types – B, E, J, K, L, N, R, S, T
Standards IEC
584-1
CJC rejection
30:1 typical
External resistance
100
Ω
maximum
RESISTANCE THERMOMETER
– 2 or 3 Wire
Standards IEC
751
(100
Ω
0°/138.5
Ω
100°C Pt)
Bulb Current
0.2mA maximum
LINEAR PROCESS INPUTS
Linear Input
Typical Accuracy
Range
0-50mV
±0.1%
± 0.00 – 99.99, ±100.00 – 499.95,
±500 – 999.9, ±1000 – 9999
4-20mA ±0.1%
As
above
0-5V ±0.1% As
above
0-10V ±0.1% As
above
APPLICABLE TO ALL INPUTS
(SM = Sensor maximum, FS=Full scale)
Calibration Accuracy
±0.1% FS typical ±1°C
Sampling Frequency
Input 10Hz, CJC 4sec
Common mode rejection
Negligible effect up to 140dB, 240V, 50-60Hz
Temperature coefficient
50ppm/°C SM typical
OUTPUT DEVICES
Solid state relay driver : SSd1 and SSd2
12Vdc +10/-15% 20mA
Miniature power relay: Rly1, Rly2, Rly3
2A/250ac resistive load, form A/SPST
Analogue Output
4-20mA 500
Ω
max ±0.1% FS typical
0-5Vdc 10mA 500
Ω
min ±0.1% FS typical
0-10Vdc 10mA 1K
Ω
min ±0.1% FS typical
LOGIC I/O MODULE :
Input Range
0-5 / 0-10 / 0-24 Vdc (s/w select)
Outputs SSd1 and SSd2
Rly1, Rly2, Rly3
12Vdc +10/-15% 20mA
2A/250ac resistive load, form A/SPST
Maximum counter input frequency
1 fast 1KHz, Other 10Hz
Accuracy ±1%
ENVIRONMENTAL:
Safety EN61010,
UL and CSA approvals pending
Measurement
Categories II and III
Pollution Degree
II
EMC Emission
EN61000-6-3
EMC Immunity
EN61000-6-2
Mouldings Flame
retardant
polycarbonate
Weight
(including connectors)
Base unit – 170g, 6oz
Control module – 90g, 3.2 oz
Ambient* 0
to
55°C
Humidity
90% max non-condensing
Altitude
Up to 2000m
SUPPLY:
Supply voltage
18-30Vdc, 8 watts ±10% fluctuation permitted
*
Note
: As with all electronic devices, product life is reduced at high ambient temperatures.
Ensure that your control panel sufficiently cooled to maximise product life.
Safety and Warranty Information
Installation
EN6110-1 / UL61010C-1 / CSA 22.2 No 1010
To offer a minimum of basic insulation only
Suitable for measurement within category II and III and pollution degree 2
See Electrical installation
It is the responsibility of the installing engineer to ensure this equipment is installed as specified in this
manual and is in compliance with appropriate wiring regulations.
Configuration
The controller can only be configured using CALogix-sw or CALgrafix software. It is the responsibility
of the installing engineer to ensure that the configuration is safe.
Ultimate Safety Alarms
Do not use SP2/SP3 or logic module outputs as the sole alarm where personal injury or damage may
be caused by equipment failure.
Warranty
CAL Controls warrant this product free from defect in workmanship and materials for three (3) years
from data of purchase.
1.
Should the unit malfunction, return it to the factory. If defective it will be repaired or replaced
at no charge.
2.
There are no user serviceable parts in this unit. The warranty is void if the unit shows
evidence of being tampered with or subjected to excessive heat, moisture, corrosion or
other misuse.
3.
Components which wear or damage with misuse are excluded e.g. relays.
4.
CAL Controls shall not be responsible for any damage or losses however caused, which
may be experienced as a result of the installation or use of this product.
CAL Controls liability for any breach of this agreement shall not exceed the purchase price paid.
E & O.E.
CAL Controls Ltd
Bury Mead Road, Hitchin,
Herts, SG5 1RT, UK
Tel +44 (0) 1462 436161
Fax +44 (0) 1462 451801
e-mail [email protected]
www.cal-controls.com
CAL Controls Inc
1117 S. Milwaukee Av,
Libertyville, IL60048, USA
Tel (847) 680-7080
Fax (847) 816-6852
e-mail [email protected]
www.cal-controls.com
33086/01/0104