FUNCTIONS AND OPTIONS TABLE
Please read these Important notes first
1. Factory setting:
is Option 0
(except Functions 2 ond 22)
2. Initial configuration
:
Functions
1
6-24 must be selected first then
entered into memory by exiting Program
mode •
see 4
then Autotune and other
Functions may be selected
Fn Opt
No. No.
Parameter
OPERATING MODE
... Protected
0 Operating mode
2
3
4
5
6
0
1
2
3
4-100
Normal Operation
Start Autotune AT
Start Autotune PT
Pork mode
Manual heat %
USER SETTINGS
... Unprotected
Manual Reset
( OUT IN PIO)
1
°
steps (mox ±127
°
/50% prop bond)
SP2 Adjust
1 ° steps
Factory setting 5
°
SP 2 mode must be selected in
Function 19
before
adjusting SP 2
SP 2 mode (Fn 19) ��on
Function
2ronge
Deviation alarm
Full scale alarm
Cool strategy
1- 3
4-5
7
0-127
°
0-*
±1270
( * Sensor range
:
Fn 16)
SP1 Lock
O
Unlocked
1
Locked
OPERATIONAL PARAMETERS
... Protected
SPl Proportional cycle time
O 20 sec
1 1 sec
2
5 sec
3
10 sec
4
30 sec
5
60 sec
6
0.05 sec
7
ON/OFF
8
0.3 sec
9
2 sec
SP1 Proportional
band/Gain
0 2.5'- CR
1
0
.
5%
2
1%
3
2%
4
3%
5
5%
6
10%
7
20%
8
1.5%
9
4%
10 6%
11 7%
12
8%
13
14%
14 100%
15
�
AT value
...
10 3 sec
11
7
sec
12 14 sec
13 45
sec
•
14
a
...
15
-
Operational
AT value
Latest
calculated
AT value
SPl Hysteresis
In
ON/OFF mode
1.25'-
025%
0.5%
1%
1.5%
2.5%
5%
10%
0.75%
2%
3%
3 5%
4%
7%
50%
SPl Derivative time/Rate
0 25 sec
1
OUT
2
5 sec
3
10 sec
4
50 sec
5
100sec
6
200sec
7
1 sec
8
2 sec
9
3 sec
10
7 sec
11
15 sec
12
20 sec
13 35 sec
14
75 sec
•
15
�
AT value
3. Protected Functions:
All Functions, except User Settings (Functions
l. 2. 3) may be locked in memory otter
setting to prevent tampering .
See 14
Parameter lock
4. AT values
(marked
•
):
As calculated on the latest AT or PT run
Fn Opt Parameter
No . No .
OPERATIONAL
PARAMETERS
... continued
7
SPl DAC
approach control
8
0 1.5
x prop bond
5
1
0.5
6
3.0
4 0
2
1.0
3
2.0
4
2.5
SPl Integral time
0 5 mln
1
OUT
2
O.Smin
3
lmin
4
2min
5
3min
6
lOmin
7 18min
•
7
•
AT value
•
8
O.2min
9
7min
10
13 min
11 25 min
12 33 min
13
43 min
..
14
a
AT
value
..
9
Sensor error correction
1
°
steps (±127
°
max)
10 SP 2 Proportional cycle time
0 ON/OFF
1 1 sec
2
5 sec
3
10 sec
4
20 sec
5
60sec
6
0.05sec
7
30 sec
8
2 sec
9 3 sec
10 7 sec
11 14 sec
12 45 sec
Non linear ranges
for Cool
strategy
13 0.15-10 sec
14
0.15-20 sec
15 0.06-15 sec
11
SP2 Proportional
band/Gain
SP2 Hysteresis
In
ON/OFF mode
0 2.5o/.
CR
1
0.5%
2
1%
3
2%
4
3%
5
5%
6 10%
7
20%
8
1.5%
9
4%
10
6%
11
7%
12
8%
13
14%
14 100%
1.25%
0.25%
0.5%
1%
1.5%
2.5%
5%
10%
0.75%
2%
3%
3.5%
4%
7%
50%
12 LBA ... Loop
break
alarm -time
0 OUT
1 1 min
2
2min
3
4min
4
6min
5
8min
6
lOmin
7
15min
8 2Omin
9
3Omin
10
4Omin
11 50 min
12
7Omin
13
9Omin
Recommended
Initial setting:
14 2 x Operational
Integral time
15
Reset Functions O
-
24 to factory
settings
O Normal
1 Reset (Function 22 not reset)
Abbreviations:
Fn
-Function
Opt"
- Option
SR
-Sensor range
CR
-Configured range
5.
Locating Functions:
Function O is the Program mode entry point
Pressing
.&
increments
T
moves direct to Function 13
for access to higher Functions
Hold pressed to auto Index through table
(Functions 13. 14, 25 ore unused)
Jg_
���
Parameter
INITIAL CONFIGURATION
... Protected
16 Sensor
Select
and
Range Table
Range Table
Type
TIC
1 J
2
K
3
N
4
R
5
S
6
T
7
E
8
L
10 B
RTD
Factory set
oc
400
400
400
1600
1600
250
500
400
1600
Of
800
800
800
1999
1999
500
1000
800
1999
9
PTlOO
200
400
Sensor
range (SR)
oc
Of
800
1470
1200
1999
1200
1999
1600
1999
1600
1999
250
500
600
1100
800 1470
1800 1999
400 750
Range
minimum: O
°
C/32
°
F
Except T /P
TI
OO
·
Factory set O
°
C/32
°
F
Minimum available -200 ° C/
°
F
Linear process inputs
11 0 -20mV
12
4 - 20mV
13
0 - 20mV
14
4
-
20mV
15
0 - 2OmV
Display
0-100
0-100
0-1000
0-1000
0-2000
17
Negative temperature ranging
O Disabled
1 Enabled (range min -200
°
)
18 Display resolution
O Normal
(1
°
)
1 Hi-res ( 0.1
°
) ±199.9
°
1
°
settings become 0.1
°
Ronged O - 200 ° on selection
of Hi -res . (reset with Fn 24)
19 SP2 Operating mode
Select and enter Function 19
before
adjusting SP 2 In Function 2
0 OUT
1 Deviation alarm - High
2
Deviation alarm -Low
3 Deviation bond olorm
4
Full scale alarm -High
5
Full scale alarm
-
low
6
LBA - Loop breol< alarm
7 Cool strbtegy
20 SPI Sensor break
O Upscale
1 Downscale
21 SP2 Sensor break
O Upscale
1 Downscale
22
°
C/
°
F
( Note Change top fascia)
O
° C i Factory set
1
°
F
l
not reset by Function 15
23
Software version number
24 Configured range (CR) adjustment
1
°
steps
Mode B adjustment
see
4.2
(See Range Table In Function 16)