17
SHELL UP - SHELL PS -BREEZE AIRTIGHT
8.8
SWITCH OFF (ON PANEL: OFF WITH FLASHING FLAME)
If the shutdown key is pressed or if there is an alarm signal, the boiler goes into the thermal shutdown phase which entails the
automatic execution of the following stages:
• Pellet loading is stopped.
• The room fan continues to operate until the requested temperature is reached.
• The flue fan is set to its highest value, which it keeps until the requested temperature is reached, plus a safety time of 10
additional minutes. After that, if the fume temperature has decreased below the switch off threshold, it stops, otherwise the
cooling process goes on.
• If the stove has switched off normally, but owing to thermal inertia, the fume temperature goes over the threshold again, the
switch off process is reactivated until the temperature decreases again.
8.9
POWER FAILURE
• After a black-out lower than 10 seconds, the stove turns back to the power which was settled.
• After a black-out of more than 10 seconds, the stove enters the during shutdown. Completed this phase, it starts automatically
up with the different phases.
8.10 ADJUSTMENTS MENU
To access the adjustments menu act as follows:
• Press the + - keys
• Scroll with the <> arrows and select “Set Room T ” or “Air Fan Speed 1” or “Air Fan Speed 2” or “Comfort Mode” or "Fire"
• Press “menu” to access the selected option.
• Modify with the + - keys.
• Press “menu” to confirm and “esc” to exit.
Set Room T.
- this function allows setting the desired temperature in the room where the stove is installed, starting from a mi-
nimum of 5°C up to a maximum of 35°C. When this condition is met, the stove reaches the minimum consumption values (flame
and hot air fan speed at minimum values) and then goes back to theset values when the ambient temperature goes below the set
threshold (see
Fig. 13
).
Fig. 13 - Display
Note: The full stop to the right of the ambient temperature shown in the control panel display (upper right) indicates the half
degree (e.g. 23.° means 23.5°C).
Air Fan Speed 1 -
this function allows selecting the desired speed for the ambient fans from 1 to 5 or A. A means automatic,
ventilation depends on power, recommended setting (see
Fig. 14
).
Air Fan Speed 2
- (ONLY FOR STOVES WITH DUCTING) this function allows selecting the desired speed for the DUCTING fans from
1 to 5 or A. A means automatic, ventilation depends on power, recommended setting (see
Fig. 15
).
Air Fan Speed. 3
- (ONLY FOR STOVES WITH DUCTING) this function allows selecting the desired speed for the DUCTING fans from
1 to 5 or A. A means automatic, ventilation depends on power, recommended setting (see
Fig. 16
).
Fig. 14 - Display
Fig. 15 - Display
Fig. 16 - Display
With function “1” or "2" or "3" or "4" or "5" the fan is forced to work at the selected output. (For example: by setting “3”, even if the
fan is set to heat output 5 it will work as if set to heat output “3”, etc.).