The Steam Humidifier delivers humidity in the form of steam to the 
conditioned space via the HVAC system duct . The humidifier generates 
steam by energizing two electrodes that extend into a canister of water . 
Current flowing between the electrodes causes the water to boil, creating 
steam . Water is introduced to the humidifier through a fill valve to a fill 
cup located in the top of the cabinet . The fill cup serves as an overflow 
reservoir and provides an air gap between the humidifier and water 
source . The steam canister is filled from the bottom . The canister is seated 
in a drain cup assembly which includes a drain valve . The drain and fill 
valves work together to maintain water level in the canister to deliver the 
rated steam capacity based on the electrical conductivity of the water and 
to temper drain water . See 

Figure 1

 for representation of fill and drain 

system and canister . 
Steam is delivered into the airstream through a dispersion tube mounted 
in the HVAC system ductwork . Openings in the dispersion tube are fitted 
with “tubelets

” which extend into the center of the tube . The design of 

the dispersion tube and tubelets distribute steam over a wide area in the 
duct and direct any condensed moisture back into the steam hose .

PRINCIPLES OF OPERATION

FIGURE 1 – Fill and Drain System and Canister

90-1522

 

Steam

Outlet

Drain

Supply

Water

Drain Cup

Drain Valve

Canister

Electrodes

High Water

Level Sensor

Flow Control

Orifice

Inlet

Fill Valve

Overflow

Fill

Fill Cup

Thank you for your recent steam humidifier purchase . We appreciate 
your business and are pleased to add your name to our growing list of 
customers . You have invested in the highest quality equipment available . 
Your humidifier will require periodic maintenance to assure continued 
consistent performance . See page 10 .
Please take a few minutes and read this booklet . This will familiarize 
you with the benefits you will receive from the humidifier and help you 
understand the routine maintenance that will be required . 

INTRODUCTION

Replacement Steam Canisters are available from your installing 
contractor. Use only genuine replacement part number 8045HUM. 

SEQUENCE OF OPERATION

When the Humidifier Control detects humidity below the set point, 
and provided the humidifier is turned on and the indoor unit blower is 
operating, the internal controller in the humidifier energizes the electrodes 
and measures the current flowing through the water between them . The 
controller adjusts water level in the canister via a fill valve and a drain 
valve to maintain a constant current . The operating water level in the 
canister depends on the mineral content of the water which determines 
conductivity .
A relay is provided with the humidifier that will allow the control to turn 
on the indoor unit blower when a call is made for humidity .

Summary of Contents for HUM STM3034 Series

Page 1: ...READ AND SAVE THESE INSTRUCTIONS Model HUMCRSTM3134 HUMXXSTM3034 HUMXXSTM3134 Residential Steam Humidifier Owner s Manual Includes Safety Operating Instructions Residential Steam Humidifier...

Page 2: ...until electrical power is disconnected Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system ELECTRICAL SHOCK HAZARD If the humidif...

Page 3: ...and Canister 90 1522 Steam Outlet Drain Supply Water Drain Cup Drain Valve Canister Electrodes High Water Level Sensor Flow Control Orifice Inlet Fill Valve Overflow Fill Fill Cup Thank you for your...

Page 4: ...s time the Steam light illuminates green If the humidifier cannot produce steam at the rated level after trying for 168 hours the Steam light illuminates yellow The humidifier continues to operate in...

Page 5: ...ent level below 75 of the maximum operating current Humidifier continues to operate but at reduced capacity Solid Red Operational problem with humidifier Humidifier shuts down Occurs when unit detects...

Page 6: ...HOCK HAZARD Disconnect main electrical power to the humidifier at the circuit breaker and drain the water from unit before servicing Hot surface inside NOTICE Service should be performed by an HVAC te...

Page 7: ...w O ring O ring is provided with Model 8045HUM canister into slot in drain assembly Dampen O ring with water before inserting canister Do not use oil grease or any lubricant besides water 12 Make sure...

Page 8: ...er relay One wire either one but not both must go through current sensing toroid see FIGURE 3A Electrode wires are interchangeable and can be placed on either of the two terminals FILL VALVE SERVICE 1...

Page 9: ...Catalog No OM HUMCRSTM 02 10016625 B2210113B 02 23 2023 CAC BDP 7310 West Morris St Indianapolis IN 46231...

Reviews: