XFP ENGINEERING MANUAL • Approved Document No. DFU2200502 Rev 1 • Page 8 of 8

XFP 32 ZONE REPEATER PANEL

TECHNICAL SPECIFICATION

Mains supply voltage: 

230V a.c. ± 10% 50/60Hz

Internal power supply:

27V d.c Nominal

Total output current limited to:

3A @ 230V a.c.

Supply and battery charger monitored for failure: Yes
Batteries monitored for disconnection and failure: Yes
Batteries protected against deep discharge:

Yes

Max. battery size and type:

3.2 AHr VRLA

Temperature compensated charging:

Yes

Mains fuse:

1A HRC Ceramic 20mm

Battery fuse:

3A F 20mm

Physical dimensions:

410 x 250 x 80mm (back box); 439 x 274 x 7mm (lid)

Approx weight:

4.5kg (without batteries)

Cabling requirements:

1.5mm

2

two core fire resistant, screened

Max. no. of repeaters:

8

Max. cable length per repeater network:

500m

Summary of Contents for XFP510-32

Page 1: ...XFP 32 ZONE REPEATER PANEL installation manual approved document no DFU2200502 Rev 1...

Page 2: ...nge of fire panels for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy is one of continuous improvement and we reserve...

Page 3: ...n Installation Commissioning and Maintenance available at your local reference library or from the BSI Other national standards of installation should be referenced where applicable Cable types and li...

Page 4: ...the telecoms style lid base connecting cable from PL5 on the Main Control PCB Care should be taken when detaching the connector to depress the locking tab to prevent damage XFP ENGINEERING MANUAL App...

Page 5: ...note that an optional bezel part no AFP735 is available for semi flush mounting To expose the mounting holes you must first remove the panel s lid and base PCBs as described on page 5 The mounting ho...

Page 6: ...within the panel Fig 3 Power Supply PCB layout and Mains connection details Incoming Mains cable must be segre gated from other cables and should only enter the panel through either of these knockout...

Page 7: ...LT SYSTEM FAULT SOUNDER STATUS DE RU Auxilliary 24V I P1 I P2 0v Relay 1 NC C NO Relay 2 NC C NO Relay 3 NC C NO Fault NC C NO Sounder Circui 1 2 REMOVING THIS CIRCUIT BOARD EXPOSES HAZARDOUS VOLTAGES...

Page 8: ...red for failure Yes Batteries monitored for disconnection and failure Yes Batteries protected against deep discharge Yes Max battery size and type 3 2 AHr VRLA Temperature compensated charging Yes Mai...

Reviews: