ENABLE/DISABLE RELAYS

This  function  allows  the  disablement  of  one  or  more  of  the  panel’s  3  auxiliary  relays  from  activating  as
programmed.  When selected, press the Accept

4

button and a window similar to the one below will appear:

Select the relay (1, 2 or 3) to be disabled/enabled using the 

5

and 

6

buttons. 

When the desired relay has been selected, press the Accept

4

button and the relay’s status (Enabled or

Disabled) will flash.  Next, use the 

5

and

6

buttons to toggle between enabled and disabled and press

the  Accept

4

button  to  select  the  desired  option.  The  window  will  now  move  to  the  next  relay

allowing  further  enablements  or  disablements  to  be  made.  Alternatively,  to  return  to  the  previous
menu press the Escape

3

button.

ENABLE/DISABLE DEVICES

This  function  allows  loop  devices  to  be  disabled  from  reporting  faults,  fires,  pre-alarms,  etc.,  and  is
normally used to temporarily disable detectors/call points that are nuisance tripping. When selected,
press the Accept

4

button and a window similar to the one below will appear:

Use the 

5

and

6

buttons to select the zone where the device you wish to disable/enable is located.

When selected, press the Accept

4

button and a list of all devices that can be disabled or enabled in

that zone will appear, e.g.

Use the 

5

and

6

buttons to scroll through the available devices.  When the desired device appears,

press  the  Accept

4

button  and  the  device’s  status  (Enabled  or  Disabled)  will  flash.    Next,  use  the

5

and

6

buttons to toggle between enabled and disabled and press the Accept

4

button to select the

desired  option.    The  window  will  now  move  to  the  next  device  allowing  further  enablements  or
disablements to be made.  Alternatively, to return to the previous menu press the Escape

3

button.

Please note: if all the input devices on a zone are individually disabled, the zone they belong to will also
be disabled.  If you try to re-enable a zone which has no enabled devices on it using the ENABLE/DISABLE
ZONES function described on page 17, a prompt appears saying this cannot be done.  Instead you must
first enable at least one device on the zone before re-enabling the zone itself.

ENABLE/DISABLE FAULT RELAY

This function can be used to suppress the panel’s fault relay from activating in a fault condition. When
selected, press the Accept

4

button and the following window will appear:

Use the 

5

and

6

buttons to toggle between enabled and disabled and press the Accept

4

button to

select the desired option.  Alternatively, to return to the previous menu press the Escape

3

button.

ENABLE/DISABLE OUTPUT DELAYS

This function can be used to globally disable or enable any delays to outputs that have been programmed
into the panel. When selected, press the Accept

4

button and the following window will appear:

Use the 

5

and

6

buttons to toggle between enabled and disabled and press the Accept

4

button to

select the desired option.  Alternatively, to return to the previous menu press the Escape

3

button.

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 18 of 28

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

Select Zones:- 1: Shop Floor

Shop Floor:- 1: Gent WC
Loop 1, Device 3: Enabled

Fault relay is:- Enabled

Panel Relay:- 1

Delays to Outputs are:- 
Enabled

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for XFP502/X

Page 1: ...XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL user manual and log book Approved Document No DFU2000510 Rev 1 www acornfiresecurity com www acornfiresecurity com...

Page 2: ...el 1 general user controls and menu options 12 Displaying fire fault disablement and test events 12 13 Testing the panel s lamps 13 Displaying the panel s alarm counter 13 Access level 2 authorised us...

Page 3: ...s separate engineering manual and have the necessary skills for maintaining this equipment If the enclosure is damaged in any way expert advice should be sought regarding its repair Regular servicing...

Page 4: ...stem enters day building occupied and night building unoccupied mode and to test the panel s indicators and liquid crystal display to ensure they are working correctly All of these functions and more...

Page 5: ...alarms 47h 8 Ensure that any structural or occupancy changes planned for the building are done so with due and early consideration given to any changes that may be required to the fire system 47h 9 E...

Page 6: ...ent test sounder status power supply fault general fault system fault delays running supply present more information escape accept 10 59 03 24 Jun Normal FREDCO WAREHOUSING Fire Zones 17 18 19 20 21 2...

Page 7: ...re on the system Delays Running Lit yellow when one or more output delays have been programmed into the panel Flashes yellow when one or more output delay is running Button controls More Information D...

Page 8: ...igger in the event of a fire alarm condition for a set period of time as programmed by the system engineer Pressing the More Information button in a fire alarm condition will give more information abo...

Page 9: ...ll now appear on a step by step basis with details of which order they went into fire i e 1st zone 2nd zone etc Pressing the More Information button at any time will give you details of the actual dev...

Page 10: ...t up with an investigation delay period Press the More Information button to display the actual device that has triggered the 1st stage fire condition pressing More Information again will count down h...

Page 11: ...the More Information button to view additional details about the displayed fault For device specific faults the actual device that has triggered the fault condition will be shown For other faults inf...

Page 12: ...rd of any changes should appear on the System Set Up Data Chart on page 20 of this user manual If they do not contact your maintenance company for advice As soon as the code has been entered correctly...

Page 13: ...licable can be viewed by pressing the panel s More Information button To return to the main access level 1 menu press the Escape3button Testing the Panel s Lamps This function tests the panel s lamps...

Page 14: ...ition I Silencing the alarm sounders To silence any active alarm sounders enter access level 2 see above and momentarily press the Silence Resound Sounders button The alarm sounders will cease to soun...

Page 15: ...number of times the panel has been in a fire alarm condition When selected press the Accept4button and the display will show the total number of times the panel has been in a fire condition since it w...

Page 16: ...NT HISTORY menu option when selected displays the panel s 500 event log on the display For example Initially only the last event will appear in the window but you can scroll through the list using the...

Page 17: ...self ENABLE DISABLE SOUNDERS This function allows you to disable one or more sounder groups from sounding in a fire condition When selected press the Accept4button and a window similar to the one belo...

Page 18: ...lect the desired option The window will now move to the next device allowing further enablements or disablements to be made Alternatively to return to the previous menu press the Escape3button Please...

Page 19: ...the code again by pressing the 5 1 4 2 6 3 3 4 buttons in same sequence If the two codes match the panel will accept the code and you will be taken back to access level 2 If you type an incorrect con...

Page 20: ...s of the 6key If this code is changed make a note of the changes here New access level 2 code Date changed __________________ ADDITIONAL INFORMATION We recommend any additional information the user ne...

Page 21: ...ills Dates and times of all fires to which the system responds Dates and times of all false alarms Causes circumstances surrounding and category of false alarms if known The identity of any manual cal...

Page 22: ...etails of tests including fire drills actual fire alarms disablements or enablements and faults should be recorded here False alarms and maintenance work should be recorded on page 26 DATE TIME EVENT...

Page 23: ...ent No DFU2000510 Rev 1 Page 23 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS www acornfir...

Page 24: ...ent No DFU2000510 Rev 1 Page 24 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS www acornfir...

Page 25: ...ent No DFU2000510 Rev 1 Page 25 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS www acornfir...

Page 26: ...IRCUMSTANCES where cause is unknown record activities in the area MAINTENANCE VISIT REQUIRED YES or NO FINDINGS OF MAINTENANCE TECHNICIAN CATEGORY OF FALSE ALARM FURTHER ACTION REQUIRED DONE PLEASE TI...

Page 27: ...ignatures below for the installation of the fire alarm system particulars of which are set out below CERTIFY that the said installation for which I we have been responsible complies to the best of my...

Page 28: ...etters Position in block letters Signature Date For and on behalf of Address postcode The extent of the liability of the signatory is limited to the system described below Extent of system covered by...

Reviews: