FIRE ALARM

ancillaries

4 of 4

Approved Document No. DFU0388010 Rev 2

FP8E 

TECHNICAL SPECIFICATION

E&OE. No responsibility can be accepted by the manufacturer or distributors of this equipment for any misinterpretation of this instruction, or for the compliance of the system as a
whole. The manufacturers policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice.

POWER SPECIFICATION

MAINS SUPPLY VOLTAGE

INTERNAL POWER SUPPLY

TOTAL OUTPUT CURRENT LIMITED TO

AUXILIARY POWER OUTPUT

 

 

MAINS SUPPLY MONITORED FOR FAILURE

BATTERY CHARGER MONITORED FOR FAILURE

LEAD ACID BATTERIES MONITORED FOR DISCONNECTION / FAILURE

DETECTOR CIRCUIT SPECIFICATION

NUMBER OF CIRCUITS

 

 

LINE FAULT MONITORED FOR OPEN CIRCUIT

LINE FAULT MONITORED FOR SHORT CIRCUIT

LINE FAULT MONITORED FOR DETECTOR REMOVAL

END OF LINE RESISTOR (SUPPLIED)

DETECTOR CONTINUITY DIODES

CALL POINT RESISTOR (NOT SUPPLIED)

MAXIMUM NUMBER OF SMOKE/HEAT DETECTORS PER ZONE

MAXIMUM NUMBER OF MANUAL CALL POINTS PER ZONE

SOUNDER CIRCUIT SPECIFICATION

NUMBER OF CIRCUITS

 

END OF LINE RESISTOR (SUPPLIED)

LINE FAULT MONITORED FOR OPEN CIRCUIT

LINE FAULT MONITORED FOR SHORT CIRCUIT

OUTPUTS FUSED AT

MAXIMUM TOTAL OUTPUT CURRENT (ALL OUTPUTS)

MAXIMUM NO. OF BELLS @ 25 mA EACH

 

MAXIMUM NO. OF ELECTRONIC SOUNDERS @ 20 mA EACH

 

FUSES 

- ALL FUSES COMPLIANT TO IEC (EN 60127 PT2)

MAINS TERMINAL BLOCK

 

 

SOUNDER OUTPUTS (F2, F3)

BATTERY FUSE (F1)

 

 

 

DOOR RETAINING MAGNETS

CONNECTION BLOCK

LARGEST ACCEPTABLE CONDUCTOR SIZE

SMALLEST ACCEPTABLE CONDUCTOR SIZE

 

 

PHYSICAL

ENCLOSURE (WIDTH x HEIGHT x DEPTH)

WEIGHT (WITHOUT BATTERIES)

 

 

   

 

 

 

 

These quantities are examples only.

}

FP8E (1.4A SUPPLY)

27 V d.c. nominal

1400 mA

27 V d.c. nominal
YES

YES

YES

8

YE S

YES (can be disabled)
Yes, if End of Line Monitoring Unit fitted in place of End of Line Resistor

 

6800 

Ω

, 5% tolerance, 0.25 W (colour code - blue, grey, red, gold)

 

   

 

Silicon 1N4001 or Schottky type (required if End of Line Monitoring Unit fitted)

 

470 to 680 

Ω

, 0.25 or 0.5 W

No limit

2

6800 

Ω

, 5% tolerance, 0.25 W (colour code - blue, grey, red, gold)

YES

YES

1 A

 

1400 mA

56

70

400 mA T 20 mm

1 A F 20 mm

1.6 A F 20 mm

DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME.

 

2.5 mm

2

0.75 mm

2

405 x 267 x 92 mm

5 Kg

Important: Exceeding the fuse ratings may render the equipment
unsafe and damage the output of this equipment.  This damage
is factory detectable and is not covered under warranty.

20 (maximum detector current = 2 mA)

DETECTOR CIRCUIT SPECIFICATION

POWER SPECIFICATION

SOUNDER CIRCUIT SPECIFICATION

FUSES 

- ALL FUSES COMPLIANT TO IEC (EN 60127 PT2)

CONNECTION BLOCK

PHYSICAL

IP RATING (to EN 60529)

IP30 (when correctly installed)

}

CONTROLS

EXTERNAL PUSHBUTTONS (KEYSWITCH ACTIVATED)

RESET / RESOUND / TEST ZONE LAMPS
SILENCE ALARM SOUNDERS

 

EVACUATE

INTERNAL

Revert to short circuit = fire (no resistors in Call Points).

OUTPUTS

 

 

2 sounder circuits (Alarm relay contacts can be obtained
by connecting an RLP-24 relay to a sounder circuit).

Ancillary connections for expansion modules will allow the
following: (1) Repeater Panels; (2) Multiple sounder outputs;
(3) Connection to Landlord’s Panel.

SILENCE FAULT SOUNDERS

Engineer Detector Test

 

Zone Isolate

AUXILIARY RELAY CONTACTS (DO NOT CONNECT MAINS VOLTAGES)

1A 30 V d.c. max. Voltage-Free

AUXILIARY OUTPUT (F4)

1 A F 20 mm

ANCILLARIES 

(Individual datasheets available on request)

ANCILLARIES 

(Individual datasheets available on request)

REPEATER PANEL (available in 10 and 20 zone versions)

Up to three Repeaters per control panel. Wiring = five cores plus one per zone.
Maximum cable length = 200 metres. Facilities = Common fault light; one fire light per zone;
warning buzzer; test button (test lights, buzzer & interconnecting wiring).

4 ZONE MONITORED SOUNDER EXTENDER KITS

RLP-24 5A RELAY ON PLATE (Fits single gang back boxes)

Connects to existing sounder circuits to provide four additional monitored sounder circuits.

General purpose polarised and suppressed relay for use with 24 volt fire alarm systems. Can switch Mains loads.

FLUSH BEZEL

Order Code: FF385

QUIESCENT CURRENT / BATTERY STAND-BY TIME (HRS)

1.4

STAND-BY TIME (HRS) 2.6 Ah BATTERIES

27
47

STAND-BY TIME (HRS) 4.0 Ah BATTERIES

70

QUIESCENT CURRENT (mA)

The quiescent currents

 listed are for the following conditions - Mains Supply 

failed, detector and sounder End of Line resistors fitted, no other loads

supplied by the panel. 

The battery stand-by times

 are guidelines only based

on the above conditions and a full sounder load for 30 minutes.

Additional loads that increase the quiescent current in the normal alarm state

and sounder loads must be considered when calculating stand-by time.

Batteries in poor condition greatly reduce stand-by time. 

MAX. LOAD CURRENT (A)

75

STAND-BY TIME (HRS) 6.0 Ah BATTERIES

8

NUMBER OF ZONES

EXTERNAL INDICATORS

MAINS ON 

ZONE FIRE

ZONE FAULT

SOUNDER FAULT

POWER SUPPLY FAULT

INTERNAL INDICATORS

OPEN CIRCUIT ZONE FAULT

SHORT CIRCUIT ZONE FAULT

ZONE ISOLATED

ENGINEER TEST SELECTED

Part No. FF388-3

OPERATING TEMPERATURE
HUMIDITY

-10

o

C to +40

o

C

5% to 95% RH (non-condensing)

ENVIRONMENTAL

ENVIRONMENTAL

220 - 230 V a.c. 

FREQUENCY

RATED CURRENT

50 Hz / 60 Hz

330 mA