FIRE ALARM
ancillaries
4 of 4
Approved Document No. DFU0388010 Rev 2
FP8E
TECHNICAL SPECIFICATION
E&OE. No responsibility can be accepted by the manufacturer or distributors of this equipment for any misinterpretation of this instruction, or for the compliance of the system as a
whole. The manufacturers policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice.
POWER SPECIFICATION
MAINS SUPPLY VOLTAGE
INTERNAL POWER SUPPLY
TOTAL OUTPUT CURRENT LIMITED TO
AUXILIARY POWER OUTPUT
MAINS SUPPLY MONITORED FOR FAILURE
BATTERY CHARGER MONITORED FOR FAILURE
LEAD ACID BATTERIES MONITORED FOR DISCONNECTION / FAILURE
DETECTOR CIRCUIT SPECIFICATION
NUMBER OF CIRCUITS
LINE FAULT MONITORED FOR OPEN CIRCUIT
LINE FAULT MONITORED FOR SHORT CIRCUIT
LINE FAULT MONITORED FOR DETECTOR REMOVAL
END OF LINE RESISTOR (SUPPLIED)
DETECTOR CONTINUITY DIODES
CALL POINT RESISTOR (NOT SUPPLIED)
MAXIMUM NUMBER OF SMOKE/HEAT DETECTORS PER ZONE
MAXIMUM NUMBER OF MANUAL CALL POINTS PER ZONE
SOUNDER CIRCUIT SPECIFICATION
NUMBER OF CIRCUITS
END OF LINE RESISTOR (SUPPLIED)
LINE FAULT MONITORED FOR OPEN CIRCUIT
LINE FAULT MONITORED FOR SHORT CIRCUIT
OUTPUTS FUSED AT
MAXIMUM TOTAL OUTPUT CURRENT (ALL OUTPUTS)
MAXIMUM NO. OF BELLS @ 25 mA EACH
MAXIMUM NO. OF ELECTRONIC SOUNDERS @ 20 mA EACH
FUSES
- ALL FUSES COMPLIANT TO IEC (EN 60127 PT2)
MAINS TERMINAL BLOCK
SOUNDER OUTPUTS (F2, F3)
BATTERY FUSE (F1)
DOOR RETAINING MAGNETS
CONNECTION BLOCK
LARGEST ACCEPTABLE CONDUCTOR SIZE
SMALLEST ACCEPTABLE CONDUCTOR SIZE
PHYSICAL
ENCLOSURE (WIDTH x HEIGHT x DEPTH)
WEIGHT (WITHOUT BATTERIES)
These quantities are examples only.
}
FP8E (1.4A SUPPLY)
27 V d.c. nominal
1400 mA
27 V d.c. nominal
YES
YES
YES
8
YE S
YES (can be disabled)
Yes, if End of Line Monitoring Unit fitted in place of End of Line Resistor
6800
Ω
, 5% tolerance, 0.25 W (colour code - blue, grey, red, gold)
Silicon 1N4001 or Schottky type (required if End of Line Monitoring Unit fitted)
470 to 680
Ω
, 0.25 or 0.5 W
No limit
2
6800
Ω
, 5% tolerance, 0.25 W (colour code - blue, grey, red, gold)
YES
YES
1 A
1400 mA
56
70
400 mA T 20 mm
1 A F 20 mm
1.6 A F 20 mm
DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME.
2.5 mm
2
0.75 mm
2
405 x 267 x 92 mm
5 Kg
Important: Exceeding the fuse ratings may render the equipment
unsafe and damage the output of this equipment. This damage
is factory detectable and is not covered under warranty.
20 (maximum detector current = 2 mA)
DETECTOR CIRCUIT SPECIFICATION
POWER SPECIFICATION
SOUNDER CIRCUIT SPECIFICATION
FUSES
- ALL FUSES COMPLIANT TO IEC (EN 60127 PT2)
CONNECTION BLOCK
PHYSICAL
IP RATING (to EN 60529)
IP30 (when correctly installed)
}
CONTROLS
EXTERNAL PUSHBUTTONS (KEYSWITCH ACTIVATED)
RESET / RESOUND / TEST ZONE LAMPS
SILENCE ALARM SOUNDERS
EVACUATE
INTERNAL
Revert to short circuit = fire (no resistors in Call Points).
OUTPUTS
2 sounder circuits (Alarm relay contacts can be obtained
by connecting an RLP-24 relay to a sounder circuit).
Ancillary connections for expansion modules will allow the
following: (1) Repeater Panels; (2) Multiple sounder outputs;
(3) Connection to Landlord’s Panel.
SILENCE FAULT SOUNDERS
Engineer Detector Test
Zone Isolate
AUXILIARY RELAY CONTACTS (DO NOT CONNECT MAINS VOLTAGES)
1A 30 V d.c. max. Voltage-Free
AUXILIARY OUTPUT (F4)
1 A F 20 mm
ANCILLARIES
(Individual datasheets available on request)
ANCILLARIES
(Individual datasheets available on request)
REPEATER PANEL (available in 10 and 20 zone versions)
Up to three Repeaters per control panel. Wiring = five cores plus one per zone.
Maximum cable length = 200 metres. Facilities = Common fault light; one fire light per zone;
warning buzzer; test button (test lights, buzzer & interconnecting wiring).
4 ZONE MONITORED SOUNDER EXTENDER KITS
RLP-24 5A RELAY ON PLATE (Fits single gang back boxes)
Connects to existing sounder circuits to provide four additional monitored sounder circuits.
General purpose polarised and suppressed relay for use with 24 volt fire alarm systems. Can switch Mains loads.
FLUSH BEZEL
Order Code: FF385
QUIESCENT CURRENT / BATTERY STAND-BY TIME (HRS)
1.4
STAND-BY TIME (HRS) 2.6 Ah BATTERIES
27
47
STAND-BY TIME (HRS) 4.0 Ah BATTERIES
70
QUIESCENT CURRENT (mA)
The quiescent currents
listed are for the following conditions - Mains Supply
failed, detector and sounder End of Line resistors fitted, no other loads
supplied by the panel.
The battery stand-by times
are guidelines only based
on the above conditions and a full sounder load for 30 minutes.
Additional loads that increase the quiescent current in the normal alarm state
and sounder loads must be considered when calculating stand-by time.
Batteries in poor condition greatly reduce stand-by time.
MAX. LOAD CURRENT (A)
75
STAND-BY TIME (HRS) 6.0 Ah BATTERIES
8
NUMBER OF ZONES
EXTERNAL INDICATORS
MAINS ON
ZONE FIRE
ZONE FAULT
SOUNDER FAULT
POWER SUPPLY FAULT
INTERNAL INDICATORS
OPEN CIRCUIT ZONE FAULT
SHORT CIRCUIT ZONE FAULT
ZONE ISOLATED
ENGINEER TEST SELECTED
Part No. FF388-3
OPERATING TEMPERATURE
HUMIDITY
-10
o
C to +40
o
C
5% to 95% RH (non-condensing)
ENVIRONMENTAL
ENVIRONMENTAL
220 - 230 V a.c.
FREQUENCY
RATED CURRENT
50 Hz / 60 Hz
330 mA