EACIE Evacuation Alert Control and Indicating Equipment 

User Manual & Log Book 

 Approved Document No. DFU5030070 Rev 1 

 

Page 5 of 10 

3  USER RESPONSIBILITIES 

BS 8629 is the British Standard code of practice for the design, installation, commissioning and maintenance of 
evacuation alert systems for use by fire and rescue services in buildings containing flats. 

Clause 22 of BS 8629 (Users’ responsibilities) states that a single, named member of the premises management 
should be appointed to supervise all matters pertaining to the evacuation alert system. 
 

BS 8629 Clause 22.1.2 states the responsible person should meet the following recommendations: 

 
a) 

ensuring that the EACIE is checked at least once every month to confirm that it is, visually, in good order 
and not indicating any faults; 

b) 

ensuring that arrangements are in place for inspection, testing and servicing of the system in accordance 
with BS 8629 Clause 21.1; 

c) 

ensuring the system log book (BS 8629 Clause 22.2 and Section 6 of this manual) is kept up-to-date and 
is available for inspection by any authorized person (e.g. representatives of the fire and rescue service); 

d) 

ensuring that all residents are instructed to report audible fault indications, and are instructed on the action 
to take in the event of operation of evacuation alert devices within their flats (i.e. instructed to evacuate 
without delay  if the evacuation alert device(s)  within their  flat is operated, and to contact the  fire and 
rescue service if they are unable to evacuate). The premises management should be advised to incorporate 
this advice within fire action notices for the building; 

e) 

establishing liaison  with residents to ensure that  material changes in the layout or internal subdivision 
within their flat do not compromise sound pressure levels or visibility of visual evacuation alert devices; 

f) 

ensuring that when changes are made to the system, record drawings and operating instructions, supplied 
in accordance with BS 8629 Clause 20.2, are updated; 

g) 

in buildings with more than one evacuation alert zone on any storey, ensuring that a suitable plan of the 
evacuation alert zones is displayed, is undamaged and is kept up-to-date (see BS 8629 Clause 13.2.2h); 

h) 

ensuring that the fire and rescue service are aware of the presence of the system, and that fire and rescue 
service crews are afforded the opportunity to familiarize themselves with the system. 

 

Familiarization visits by the fire and rescue service should not include operation of any evacuation alert signal; 
this is to avoid complacency by residents when an evacuation alert signal is given during the course of a fire. 

 
 

Six monthly inspection, testing, servicing and maintenance 

The responsible person must ensure that an ongoing six monthly plan is in place that meets BS 8629 Clause 21 
(Inspection, Testing and Servicing). The work required to meet this clause must be carried out by a competent 
person with specialist knowledge of evacuation alert systems. The standard recognises this will normally be an 
outside specialist organisation. 
 

Summary of Contents for EACIE

Page 1: ...IE EVACUATION ALERT CONTROL AND INDICATING EQUIPMENT EACIE 1 to 4 Loop Panel User Manual Log Book Approved Document No DFU5030070 Rev 1 THE EACIE PANEL IS ONLY FOR USE BY THE FIRE AND RESCUE SERVICE F...

Page 2: ...vacuation light turns red 2 Move switch UP to turn off the evacuation alert sounders The Evacuation light turns off EACIE Panel Switch Module Switch DOWN Sounders ON RED is lit Switch UP Sounders OFF...

Page 3: ...sary of terms used in this document 1 IMPORTANT NOTES 4 2 INTRODUCTION 4 3 USER RESPONSIBILITIES 5 4 CONTROLS INDICATORS 6 4 1 EACIE FRONT PANEL 6 4 2 EACIE STATUS PANEL 7 5 GLOSSARY OF TERMS 7 6 SYST...

Page 4: ...d interface the EACIE panel allows the FRS to operate evacuation alert devices located in residential flats Evacuation alert devices include sounders visual indicators and vibrating pillow pads In add...

Page 5: ...operated and to contact the fire and rescue service if they are unable to evacuate The premises management should be advised to incorporate this advice within fire action notices for the building e e...

Page 6: ...Switch Module Manual Controls Status What this means Evacuation toggle switch up to 48 off UP is OFF Deactivates evacuation alert sounders in the associated evacuation alert zone floor up to 48 off DO...

Page 7: ...ng Centre BS EN 54 2 Fire Detection and Fire Alarm Systems Control and Indicating Equipment BS EN 54 4 Fire Detection and Fire Alarm Systems Power Supply Equipment BS 8629 Evacuation Systems for Fire...

Page 8: ...S INSTALLED BY THE SYSTEM WAS COMMISSIONED BY THE SYSTEM WAS ACCEPTED BY FOR SERVICE DETAILS OF WHO YOU SHOULD CONTACT IF MAINTENANCE IS REQUIRED THE SYSTEM IS MAINTAINED UNDER CONTRACT BY Company ___...

Page 9: ...Details of any non maintenance events should be recorded here e g use by the FRS and faults Note Before entering details on this form photocopy additional sheets for future use DATE TIME EVENT e g use...

Page 10: ...Rev 1 Page 10 of 10 Details of any maintenance work should be recorded here Note Before entering details on this form photocopy additional sheets for future use DATE TIME EVACUATION ALERT ZONE DEVICE...