9.5 Setting facility code
.
3
. .
0-255
. .
#
.
This operation may be required when FP1-PROX is acting as a Wiegand reader and connecting to a multi door controller
9.6 Setting lock type and door relay time
Fail secure (unlock when power on)
.
*
. .
Master code
. .
#
. .
4
. .
0-99
. .
#
.
Fail safe (unlock when power off)
.
*
. .
Master code
. .
#
. .
5
. .
0-99
. .
#
.
0-99 is to set the door relay time to 0-99 seconds. Factory default is fail safe lock, relay time 5 seconds.
9.7 Setting door open detection
.
*
. .
Master code
. .
#
.
.
6
. .
0
. .
#
.
To disable this function (factory default setting)
.
6
. .
1
. .
#
.
To enable this function
When this function is enabled:
a)
If the door is opened normally, but not closed after one minute, the internal buzzer will sound automatically, the alarm
will turn off after one minute.
b)
If the door is forced open, or the door was not opened within two minutes of the lock being released, the internal
buzzer and external alarm will both activate.
9.8 Setting security status
.
*
. .
Master code
. .
#
.
.
7
. .
0
. .
#
.
Normal status (factory default setting)
.
7
. .
1
. .
#
.
Lock on status
If there is 10 invalid cards or fingerprints read in 10 minutes, the device will lock out for 10 minutes.
.
7
. .
2
. .
#
.
Alarm status
If there is 10 invalid cards or fingerprints read in 10 minutes, the device will alarm.
9.9 Setting two devices interlocked
.
*
. .
Master code
. .
#
.
.
8
. .
0
. .
#
.
To disable this function (factory default setting)
.
8
. .
1
. .
#
.
To enable this function
9.10 Alarm signal output time
.
*
. .
Master code
. .
#
.
.
8
. .
0 - 3
. .
#
.
Alarm time is 0 – 3 minutes, factory default is 1 minute.