6–11
Chapter 6: PLC Communications
6
EA1-TCL-M Hardware User Manual, 1st Ed., 12/09
®
Direct
LOGIC DL405 PLCs and D4-DCM Module
Panel Powered via external power supply, Port1 or Port2 Communications
PLC Compatibility & Connection Chart
PLC
C-more Micro-Graphic Panel
Family
CPU
PLC Port & Type
Panel to PLC Cabling Components Required for
Specific Port and Protocol being used.
External DC Power Supply
Using panel’s Port2
DB 15-pin - female
Protocol(s)
Supported
Components &
Network Type
Direct LOGIC
DL405
D4-430
Port 0
DB 15 pin
(female)
K-sequence
EA-4CBL-1
RS-232
Port 1
DB 25 pin
(female)
K-sequence,
Direct
NET
EA-4CBL-2
RS-232
* See Diagram 3
RS-422
D4-440
Port 0
DB 15 pin
(female)
K-sequence
EA-4CBL-1
RS-232
Port 1
DB 25 pin
(female)
K-sequence,
Direct
NET
EA-4CBL-2
RS-232
* See Diagram 3
RS-422
D4-450
Port 0
DB 15 pin
(female)
K-sequence
EA-4CBL-1
RS-232
Port 1
DB 25 pin
(female)
K-sequence,
Direct
NET,
Modbus RTU
EA-4CBL-2
RS-232
* See Diagram 3
RS-422
Port 3
DB 25 pin
(female)
K-sequence,
Direct
NET,
Modbus RTU
* See Diagram 4
RS-422
Port 2
RJ12 - 6 pin
K-sequence,
Direct
NET
EA-2CBL
RS-232
D4-DCM
Port 1
DB 25 pin
(female)
Direct
NET
EA-4CBL-2
RS-232
* See Diagram 5
RS-422
* Note: Wiring Diagrams for user constructed cables start on page 6-24.