INSTALLATION INSTRUCTIONS
C-STRIP-B-LIN Series
http://lighting.cree.com/warranty | 866.924.3645
LPN00625X0001A1
07-17-2021
TMT
NOTE:
The emergency driver and AC driver
must be fed from the same branch circuit.
Make the following Electrical Connections:
STEP 1:
a.
Connect the black fixture lead labeled
unswitched hot to the unswitched
voltage supply lead.
b.
Connect the black fixture lead labeled
switched hot to the switched voltage
supply lead.
c.
Connect the white fixture lead to the
neutral supply lead (Hot 2 for 208/240V
wiring).
d.
Connect the bare or green ground fixture
lead to the supply ground lead.
e.
If 0/1-10V Dimming is used, connect the
violet fixture lead to the supply positive
dimming lead. If dimming is not being
used ensure to cap off the violet
fixture lead. Class 1 wiring must be used
for dimming connections.
f. If 0/1-10V Dimming is used, connect the
grey or pink fixture lead to the supply
negative dimming lead. If dimming is not
being used ensure to cap off the grey
or
pink fixture lead. Class 1 wiring must be
used for dimming connections
If wiring a 2' or 4' fixture, return to appropriate
Fixture Installation section. If wiring an 8' fixture,
proceed to Step 2.
STEP 2:
Turn on the unswitched supply to the fixture.
Keep the switched voltage supply to fixture
off.
STEP 3:
Plug the female connector on the ends of the
leads from the battery into the male connec-
tor on the emergency driver. Plug should click
into place. See
Figure 16
.
WARNING:
Do NOT mate the connector on
the battery leads to the emergency driver until
unswitched AC power has been supplied to
the emergency driver.
ELECTRICAL CONNECTIONS-
Emergency Driver, No Occupancy Sensor
DIM (-)
DIM (+)
VIOLET
GREY OR
PINK
SUPPL
Y WIRING
(DIMMING OPTIONAL)
LUMINAIRE
GROUND
BARE OR
GREEN/YELLOW
LINE-BLACK
SWITCHED
LINE SWITCHED
LINE- UNSWITCHED
WHITE
NEUTRAL OR
HOT 2
LINE-BLACK
UNSWITCHED
*** MALE CONNECTOR
EM DRIVER
*** FEMALE CONNECTOR
BATTERY PLUG
*** NOTE:
Battery connection only required on 8' fixtures.
*** NOTE:
Do NOT mate male connector from the emergency driver to the
female connector from the battery until AC power is supplied to the
unswitched hot lead to the fixture
.