45
4.7.4 Supply power and start up
Only connect the breaker of MINIES on the “general distribution plate” to supply power to system.
The process:
1.
Press the “POWER” for about 10s until “POWER” light is on.
2.
While you are waiting for “POWER” light on, the “POWER”, “LOCAL”, “REMOTE” light will
licker once; this is normal behavior during the start up process.
3.
When the “POWER” light is on, you can release the “POWER” button.
4.
The “POWER” light will licker for about 1-2minutes. This means that the Mini ES is
checking itself, a normal operation during the power up process.
5.
After this process, the “POWER” and “LOCAL” lights will stay on.
6.
The process in complete.
4.7.4.1 Status Check
To check the status of “POWER”, “LOCAL” lights:
Normal status:
“POWER” and “LOCAL” buttons stay alight (as shown below)
Abnormal status:
“POWER” lickers (the communication cable of the meter has not connected)
“LOCAL” lickers (the system has not been connected to the grid or the grid doesn’t has power)
Start check
Step
Content
Requirement
Result
1
Power status
Stays Lit
2
Local status
Stays Lit
REMOTE
LOCAL
POWER