background image

B-Box H Installation Guidance   

 

16

 / 

23

 

7Connection with the Inverter 

Tools: Cross screwdriver, with even tightening torque: 

25±2.5Nm.   

Connection with the power line: Get the anode and cathode lines through the PG head, connect them into BCU case, and then install them onto the anode and cathode 

terminals respectively.   

Connection with the communication line and Ethernet cable: Open the upper cover of BCU, and connect the communication line. The definition of communication line is 

as follows:   

(Remarks: Pin 1 and 3 are 13V output, and can supply power for the inverter, or supply power to the upper BMU module when multiple sets of the products are connected 

in parallel.

 

Pin 2 and 4are for receiving inverter enable signal interface. Connect to the Ethernet interface with a network cable, and lead it out through PG head.)

 

 

 

 

Pin   

Definition   

13V+

 

EN 11V+ 

13V-

 

EN 11V- 

 RS485A 

CANH

 

RS485B

 

CANL

 

Summary of Contents for B-Box H

Page 1: ...B Box H Installation Guidance 1 23 B Box H Installation Guidance Rev 1 0_May 2017...

Page 2: ...5 1INSTALLATION INSTRUCTIONS 10 5 2 PACKING INFORMATION AND SYSTEM STRUCTURE CONFIGURATION LIST 11 5 3STRUCTURE CONFIGURATION LIST 11 5 4 INSTALLATION TOOLS 12 5 5 PERSONAL PROTECTION EQUIPMENT 12 6IN...

Page 3: ...heating or electrolytic mist Please comply with the following safety precautions and warning information If you don t fully understand any one of the following preventive measures or have any doubt pl...

Page 4: ...e operating voltage range within 200 500V It is applied in the household energy storage field and works together with high voltage inverter to realize energy storage and release Each set of batteries...

Page 5: ...B Box H Installation Guidance 5 23 Position Designation A Base B Battery C BCU A B C...

Page 6: ...t and control part which contains BCU and charge discharge relay is connected to the battery modules underneath and to inverter or BMU above Position Designation A Inverter communication interface B P...

Page 7: ...terface of inverter 3 GND Grounding terminal connected to the ground 4 Ethernet Connected to the Ethernet to complete the functions of communication and remote program update 5 Inverter communication...

Page 8: ...Interface and Terminal The battery module provides energy and sends the information about the cell voltage and cell temperature in the battery module to the upper layer BCU Pluggable terminal on the b...

Page 9: ...iguration List 4 1B Box H Configuration List with SMA Sunny Island On Grid 1 Phase on Grid Inverter Type B Plus H BCU Sunny Boy STORAGE 2 5 5 9 1 4 2B Box H Configuration List with KOSTAL On Grid 3 Ph...

Page 10: ...The safety distance is greater than 0 5m c The connecting cables for installing batteries shall be as short as possible to prevent too big voltage drop of the line d Batteries of different capacity d...

Page 11: ...stallation persons shall read the system configuration list No Item Description Qty Purpose Picture 1 Installation Manual 1 Provide guidance for field installation 2 User Manual 1 System information a...

Page 12: ...nstallation Guidance 12 23 5 4 Installation Tools Cross screwdriver M3 M10 Flat tip screwdriver M3 M6 Crimping pliers Diagonal cutters Adjustable wrench Inner hexagon spanner 5 5 Personal Protection E...

Page 13: ...B Box H Installation Guidance 13 23 6Installation of Single Cabinet First step open the battery package Pearl wool Battery Plastic bag Pearl wool Carton...

Page 14: ...B Box H Installation Guidance 14 23 Second step Take outthe battery base and BCU from the packing box the method is the same as the first step Battery Base BCU...

Page 15: ...th the base then install BCU and lock the batteries with BCU the installation is over Battery Base Stack up the assembled batteries according to the actual quantity required and lock the side lock tig...

Page 16: ...on line and Ethernet cable Open the upper cover of BCU and connect the communication line The definition of communication line is as follows Remarks Pin 1 and 3 are 13V output and can supply power for...

Page 17: ...B Box H Installation Guidance 17 23 P P GND Ethernet cable Inverter communication...

Page 18: ...f inverter 2 P The system cathode connected to the battery interface cathode of inverter 3 GND Grounding terminal connected to the ground 4 Ethernet Connected to the Ethernet to complete the functions...

Page 19: ...ame BYD product serial number for example BYD100171708 00001 password 123456789 then enter the IP 192 168 5 1 in the browser and enter the account number and password to log in 2 LAN Connect the batte...

Page 20: ...B Box H Installation Guidance 20 23...

Page 21: ...eographic location the number of system groups the quantity of batteries of one group of system etc First set related parameters such as the quantity of batteries the model of matching inverter etc cl...

Page 22: ...tem will set the parameters automatically and please wait patiently and ensure the system will not be powered off otherwise the setting might fail After setting the following interface will appear on...

Page 23: ...the air switch of battery and the system can work normally 9System Shutdown Note Please power off the inverter before shutting down the system After the system is shut down check the following items...