UK
7
condition that the raw water
complies with the water quality
requirements, it can operate at
a recovery rate of 70-80% with
softening depending on the
amount of organic material in
the water.
An easy way to check the outlet
amount from the RO-plant, is:
)
(
(%)
cov
Re
)
/
(
100
)
(
h
l
pacity
Permeateca
ery
h
l
capacity
Permeate
x
h
l
amount
Outlet
Ex.: BWT PERMAQ
®
Pro 2020
with 80 % recovery:
)
(
300
1200
80
1200
100
h
l
x
nt
Outletamou
When the desired amount of
outlet water has been obtained,
tighten the counter nuts on the
outlet valve so that it is locked. It
is important that the outlet
amount is checked after counter
nuts have been tightened to
make sure that the valve has not
moved. Both counter nuts must
be locked/tightened.
Important! The needle valve
must be locked on the pre-
scribed outlet amounts. If the
needle valve is closed so that the
outlet amount becomes reduced,
it will damage the plant mem-
branes.
7.2
Adjustment of recircula-
tion amount
Adjust the recirculation amount
by loosening the counter nuts on
the recirculation valve. Adjust
the amount of permeate so it
corresponds to the values in the
table, at a temperature between
10-25 °C.
If the temperature is below 10
°C, the capacity must be 3%
lower than normal capacity for
each degree below 10 °C.
E.g. if the feed water tempera-
ture is 8 °C, for an BWT
PERMAQ
®
Pro 2030 it means
that the permeate capacity will
be 6 % below the normal 1700
l/h, i.e. 1598 l/h.
When the requested pressure
and permeate capacities have
been obtained, check again if
the outlet amount has been
adjusted correctly. (It is recom-
mended to loosen both counter
nuts while fine-adjusting the
valves).
When both valves have been
adjusted, lock both valves with
the counter nuts. Take care not
to move the valves when tighten-
ing the counter nuts.
Important! Both counter nuts
must be locked/tightened on the
valves.
NB! After the valves have been
locked, the plant must be started
and stopped 2 times, and then
the flow shall be checked again
– the valves can then be read-
justed if necessary.
Check on the high-pressure
manometer that it shows the
correct operating pressure.
Please note that the operating
pressure may vary by different
temperatures and capacities.
B
W
T P
ER
M
A
Q
®
P
ro
P
e
rm
e
a
te
c
a
p
a
cit
y
(
l/
h
)
Outlet amount (l/h)
(with softened water)
S
u
rfac
e w
ate
r
(70% re
cove
ry
)
S
u
rfac
e w
ate
r
(75% re
cove
ry
)
G
rou
n
dw
ate
r
(80% re
cove
ry
)
2010 600
257
200
150
2020 1200
514
400
300
2030 1700
729
567
425
2040 2300
986
767
575
2060 2800 1200
933
700
2080 3300 1414 1100 825
BWT PERMAQ
®
Pro
2010
2020
2030
2040
2060
2080
Pressure after HP-pump (bar)
19
19
19,5
18
17
15
Flow after HP-pump (l/h)
1750
2425
3250
4250
5500
6125
Flow permeate (l/h)
600
1200
1700
2300
2800
3300
Flow concentrate (l/h)
150
300
425
575
700
825
Flow recirculation (l/h)
1000
925
1125
1375
2000
2000
Summary of Contents for PERMAQ PRO 2000
Page 2: ...UK 2...
Page 11: ...UK 11 Alarm Transport pump 9 2 4 Indication Level low 9 2 5...
Page 19: ...UK 19 13 1 P I Diagram...
Page 20: ...UK 20 13 2 Layout Drawings...
Page 21: ...UK 21 13 3 Wiring Diagram...
Page 22: ...UK 22...
Page 23: ...UK 23...
Page 24: ...UK 24...
Page 28: ...UK 28 13 7 Spare Parts Drawing...