Fault 3:
TP-pump is
running but no
water is
getting to the
consumer
Air in the TP-pump.
The TP-pump needs to be bled of air. Switch power OFF, fill
up the tank and turn switch power back to ON. Let the pump
run a while with a large flow in order to get the remaining air
out of the pump case.
Low water level.
Disconnect the consumer. Let the tank become completely
filled and the TP-pump will start automatically.
Fault 4:
TP-pump
starts and
stops
If the piping
connection is too
small there is a risk
of outages on the
plant due to lacking
water
pressure/amount
etc.
Replace the outlet pipe (water for consumption) with an outlet
pipe with a larger dimension.
Non-return valve is
leaks/defective.
Replace the non-return valve.
The hydrophore is
defective or lacking
air.
Replace the pressure tank and set the pre-pressure at 2.7 bar.
The hydrophore
capacity is too
small.
Contact BWT for technical advice.
Pressure switch set
incorrectly.
Set the pressure switch at 4.0 bar (Stop) and 3.0 bar (Start).