![BWT AQA perla XL Installation And Operating Manual Download Page 87](http://html1.mh-extra.com/html/bwt/aqa-perla-xl/aqa-perla-xl_installation-and-operating-manual_2836717087.webp)
87
87
EN
12 Technical Data
Water softener
Type
AQA perla XL
Nominal connection width
DN
32
Connection type
(G11/4“)
Nominal capacity in accordance
with DIN EN 14743
mol (m³ x°dH)
2 x 3,2 (2 x 18)
Peak flow when blending from 20°dH to 8°dH
m³/h
3,8
Nominal flow in accordance with DIN EN 14743
m³/h
1,6
Nominal pressure PN
bar
10
Operating pressure, min./max.
bar
2 - 8
Pressure drop at nominal flow
bar
1,0
Application
Residential units
Persons
4 - 8
4 - 16
Ion exchange material fill quantity
l
2 x 7
Max. supply of regenerative
kg
50
Approx. consumption of regenerative per
regeneration
kg
0,8
Flushing water consumption per regeneration
at 4 bar, approx.
l
40
Max. flushing water flow during regeneration
l/h
170
Regeneration time, approx.
min
37
Water temperature, min. – max.
°C
5 - 25
Ambient temperature, min. – max.
°C
5 - 40
Humidity
non condensing
Mains power
V/Hz
230/50-60
Unit voltage
VDC
24
Power during operation
W
2,6
Max. power during regeneration
W
40
Max. fault message output
VDC / A
24/0,5
Protection class
IP54
Operating weight if filled to max.
kg
102
Shipping weight, approx.
kg
39
Production number AQA perla XL CN
PNR
6-500128
Production number AQA perla XL INT
PNR