BÜTTNER ELEKTRONIK – power line pure sinewave inverter
EN
31
3 Function
i
In case of overtemperature, wait 5 to 10
minutes for cooling down the device befo-
re restart. In case of overload, turn off the
load and reduce the connected consumers.
LED and acoustic signals
Status
LED Inverter/
Extern
LED Check Beeper
Output 230 V
AC
Inverter Start
ON
ON (1sec)
1 x
ON
Normaler Betrieb
ON
OFF
OFF
ON
Warnung Unterspg.
ON
OFF
2 x / break
ON
Unterspannung
ON
ON
3 x / break
ON
Überspannung
ON
ON
4 x / break
ON
Übertemperatur
ON
ON
5 x / break
ON
Warnung Überlast
ON
OFF
1 x Short / break
ON
Überlast
OFF
ON
continuous
OFF
Kurzschluss
OFF
ON
continuous
OFF
Input parameters
Voltage range
Description
Normal operation
11,5 V – 14,0 V
Optimal operation
13,0 V – 14,0 V
Warning low-voltage
11,2 V – 10,7 V
beep 2 x / break
STOP Warning low-voltage
< 10,7 V +/-0,2 V
Inverter OFF, Beep 3 x / break
RESTART low-voltage
> 12,0 V +/-0,2 V
Inverter ON
STOP overvoltage
> 15,0 V
Inverter OFF, beep 5 x / break
voltage > 16 V can cause damage to the
device even if it is not in operation!
Switching back-on of inverter /
Reset CHECK display
If the inverter has stopped operation
because of one of the previously de-
scribed reasons, a manual restart can
be done. To do so the inverter has to be
either switched OFF at the device switch
or the On/Off button at the remote con-
trol
❹
has to be pressed until the red LED
is extinguished. After a short waiting time,
the inverter can be restarted.
At the reboot the inverter now checks all
the input parameters, same as each nor-
mal startup. If there is still a parameter
over or below the limit values, the start is
prevented, and the corresponding status
message is shown on LED and Beeper.