14 | Connecting values of the vacuum system VO
46
/ 52
0870S03254
_VO 0040-0080_B_-0000_IM_en
14.4
49B
Electrical data of the terminals of the control unit
Terminal
Technical information
20
Digital output
Ready for operation, open collector
18
Analog output
Output frequency
0 V = 0 min
-1
10 V = n
max
16
Digital input 6
15
Digital input 5
Free to use
14
Digital input 4
Reset maintenance counter
13
Mass digital output
5
Mass
4
Analog input 2
Busch pressure transmitter
4
…
20 mA
0
…
1 bar abs.
10
Digital input 3
Reset failure
9
Digital input 2
Opened = rotation speed control
Closed = pressure control
8
Digital input 1
Opened = stop
Closed = start
7
Ground of the digital
inputs
6
24 V output
3
Mass
2
Analog input 1
Rotation speed control:
0 V / 0 mA = n
min
= 1,200 min
-1
10 V / 20 mA = n
max
Target value of the pressure control
0 V / 0 mA = 0 bar abs.
10 V / 20 mA = 1 bar abs.
1
10 V output
A
RS485
B
RS485
Tab. 10: Electrical data of the terminals of the control unit