Parameter Description | 8
0870166596_MV0040-0080C-D_PCI_A0004_IM_de_MD
27 / 56
8
Parameter Description
In this chapter, you will find additional information on certain changeable most ad-
vanced
parameters.
8.1 Basic Parameter
P1.3 Acceleration Time 1
Ramp time referred to variation from zero frequency to max frequency.
A second acceleration time is available in P2.5.
Minimum ramp time to assure the correct pump function: 1 s
P1.4 Deceleration Time 1
Ramp time referred to variation from max frequency to zero frequency.
A second deceleration time is available in P2.6.
To use the deceleration ramp P1.14 must be set to 1.
P1.11 Control Place
Run and direction control. A second control place is programmable in P2.10.
0: I/O Terminals
1: Keypad
2: Fieldbus
P1.12 Frequency Reference Source
Define the source of frequency reference. A second reference source is program-
mable in P2.10.
0: Analogue input AI1
1: Analogue input AI2
2: PID control
3: Motor potentiometer
4: Keypad
5: Fieldbus
P1.13 Start Function
0: Ramping
1: Flying start
P1.14 Stop Function
0 = Coasting
The motor is allowed to stop on its own inertia. The control by the drive is discontinued
and the drive current drops to zero as soon as the stop command is given.
1 = Ramp
After the Stop command, the speed of the motor is decelerated according to the set
deceleration parameters to zero speed. Fall of Enable signal, when configured, always
determines stop by coasting.
P1.15 Torque Boost