5.7.1 Wiring Diagram Resistance Thermometer
Part no.:
PT100:
0651 550 436 (option)
Transmitter: 0643 536 800 (option)
Supplier reference:
PT100: Albert Balzer AG
ref. TWBa-ADX50XG1/4X90DACB
Transmitter: Hauser
ref. TMT 187-B41FJA
Maintenance procedure:
P&ID position:
TSA+/0103 “exhaust gas temp.” (op-
tion)
Wiring with transmitter:
2
1
+
-
1
2
3
4
5
6
+
-
1 = Brown ; 2 = Blue
Wiring without transmitter:
1
2
3
4
1 and 2 = Red ; 3 and 4 = White
Electrical data (PT100):
U
i
= 30 VDC ; I
i
= 100 mA ; P
i
= 0.1 (T4) … 0.75 (T3) W ; L
i
= 0.015 mH/m ;
C
i
= 280 pF/m
Electrical data (transmitter):
U
i
= 30 VDC ; I
i
= 100 mA ; P
i
= 750 mW ; L
i
= 0 µH ; C
i
= 0 pF
4 ... 20 mA
►
0 ... 300 °C
Warning signal:
a warning signal can
be set prior the trip signal.
Trip signal:
T
trip
(TSA+/0103) = 190°C
►
14.13 mA
Part no.:
PT100 : 0651 543 954
Transmitter : 0643 536 800 (option)
Supplier reference:
PT100: Albert Balzer AG
ref. : TFE/ BDAE
Transmitter : Hauser
ref. TMT 187-B41FJA
Maintenance procedure:
Procedure A [
]
P&ID position:
TSA+/0104 “oil temperature A side”
Wiring with transmitter:
2
1
+
-
1
2
3
4
5
6
+
-
1 = Brown ; 2 = Blue
Wiring without transmitter:
1
2
3
4
1 and 2 = Red ; 3 and 4 = White
Electrical data (PT100):
U
i
= 30 VDC ; I
i
= 100 mA ; P
i
= 0.1 … 0.75 W ;
Li = 0.015 mH/m ; Ci = 280 pF/m
Warning signal:
a warning signal can be
set prior the trip signal.
Trip signal:
T
trip
(TSA+/0104) = 80°C ► 8.27mA
Summary of Contents for COBRA NS 0070-0600 C
Page 38: ...Note ...
Page 39: ...Note ...