Installation | 5
0870557375_NC2000B_VR_Ex_A0002_IM_en
17 / 36
NOTICE
The admissible motor nominal speed exceeds the recommendation.
Risk of damage to the machine!
• Check the admissible
motor nominal speed (n
max
) on the nameplate of the machine
(NP).
• Make sure to comply with it.
• Consult the
Technical Data [
►
33]
to get more information.
NOTICE
The motor frequency is below 20 Hz.
Risk of damage to the machine!
• The motor nominal speed must always be higher than 1200 min
-1
(20 Hz).
NOTICE
Incorrect connection.
Risk of damage to the motor!
• The wiring diagrams given below are typical. Check the inside of the terminal box for
motor connection instructions/diagrams.
5.6.1 Wiring Diagram Three-Phase Motor (Pump Drive)
Delta connection (low voltage):
Star connection (high voltage):
NOTICE
Incorrect direction of rotation.
Risk of damage to the machine!
• Operation in the wrong direction of rotation can destroy the machine in a short time!
Prior to start-up, ensure that the machine is operated in the right direction.
The intended rotation direction of the motor is defined by the illustration below:
IN
• Jog the motor briefly.
Summary of Contents for COBRA ATEX
Page 35: ...Note...