background image

34 

 

Cleaning 

 

  Firing up cleaning time 

Fan operation time during cleaning the furnace while firing up 

  Burning off cleaning time 

Fan operation time during furnace burning off 

  Cleaning airflow 

Fan power in % during furnace cleaning in burning off and firing up 

Supervision 

 

  Supervision time 

After  this  time,  when  the  controller  is  in  SUPERVISION  mode,  the 
controller  automatically  starts  burner  burning  off.  By  settings  =  0, 
SUPERVISION mode is deactivated. 

  Feeding time 

Fuel feeding in SUPERVISION mode. It has influence on burner power 
by operating in SUPERVISION mode. Attention: the value should be as 
small  as  possible,  just  to  keep  the  flame  burning.  Too  big  value  may 
cause to boiler overheating. 

  Cycle time 

Feeder  operation  time  in  SUPERVISION  mode. 

SUPERVISION  cycle 

time

  = 

SUPERVISION  feeding  time

 

+  feeder  pause  time  in 

SUPERVISION

.

 

  Airflow power 

Fan power in % during operation in SUPERVISION mode. Adjust value 
in  such  a  way  to  burn  feeding  fuel  in  SUPERVISION  mode  with  low 
fumes emission. 

Airflow minimum power 

Minimum  fan  power  in  %,  which  can  be  chosen  by  the  user.  It  is  only 
used  to  limit  the  accessible  scope  of  fan  power.  It  is  not  used  in 
algorithm  of  controlling  the  fan.  It  should  be  possibly  small  to  allow  the 
fan to rotate slowly, without buzzing. 

Lack of detection time 

Time  is  measured  after  decrease  in  brightness  of  flame  below  value 

Flame detection %

.

 After deducting this time the controller switches into 

firing up attempt. After 3 failed attempts, it reports alarm: “Failed firing up 
attempt”. 

Feeder max. temperature 

Determines  maximum  temperature  of  feeder  when  there  is  alarm  of 
exceeding maximum feeder temperature. 

Additional feeder operation 
time 

Determines  additional  feeder  operation  time.  Feeder  is  attached  to 
additional  module  B.  After  this  time  additional  feeder  operation  is 
stopped  despite  disconnecting  joints  of  fuel  level  sensor.  Joints  of  fuel 
level sensor are located in additional module B. 

 

14.2. BOILER SERVICE SETTINGS 
 

Boiler settings

 

 

Thermostat selection 

Options to choose from: 

 

Deactivated (deactivates room thermostat influence on boiler 
operation) 

 

Universal (activates room thermostat for boiler) 

 

ecoSTER200 T1 (option available after connecting room panel 
ecoSTER200, boiler operation is depending on room thermostat 
No1 in ecoSTER200) 

 

ecoSTER200 T2 (option available after connecting room panel 
ecoSTER200, boiler operation is depending on room thermostat No 
2 in ecoSTER200 – on sensor CT7) 

 

ecoSTER200 T3 (option available after connecting room panel 
ecoSTER200, boiler operation is depending on room thermostat 
No3 in ecoSTER200 – on sensor CT7)  

Return protection* 

Group  of  parameters  available  after  connecting  return  sensor, 
responsible  for  protection  of  boiler  return  in  hydraulic  installation  with  4 
way  valve  equipped  in  mixer  servomotor,  point  9.1.  It  is  not  advised  to 
activate  functions  of  return  protection  because  it  may  cause  frequent 
stops  in  power  of  mixer  cycle.  Instead  this  it  is  recommended  to  use 
bigger preset temperatures of boiler (70-75%) what in combination with 
installation  with  4  way  valve  (with  servomotor)  it  will  cause  automatic 

Summary of Contents for RControl EM890

Page 1: ...unctions available in additional module B functions available in additional module MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 0 APPLIES FOR...

Page 2: ......

Page 3: ...ONDITIONS 22 12 CONTROLLER INSTALLATION 22 12 1 ENVIRONMENTAL CONDITIONS 22 12 2 INSTALLATION REQUIREMENTS 22 12 3 INSTALLATION 23 12 4 ELECTRIC CIRCUIT CONNECTION 23 12 5 SAFETY CONNECTIONS 24 12 6 E...

Page 4: ...4 17 4 NETWORK FUSE REPLACEMENT 40 17 5 CONTROL PANEL REPLACEMENT 40 18 LAMBDA PROBE 41 19 POSSIBLE FAULTS DESCRIPTION 42 20 CONTROLLER CONFIGURATION BY BOILER PRODUCER 43 21 CHANGES REGISTER 43...

Page 5: ...eder etc The controller is for boiler pellet burner producers The producer before its use should check if the cooperation between the controller and the boiler burner is correct and is not dangerous T...

Page 6: ...ser s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get acquai...

Page 7: ...USER MANUAL FOR CONTROLLER R Control 890...

Page 8: ...ion Automatic disinfection SUMMER Switch on temperature SUMMER Switch off temperature SUMMER Mixer settings 1 2 3 4 5 Mixer preset temperature Room mixer thermostat Mixer weather control Mixer heating...

Page 9: ...iler preset temperature increase from mixer circulation P Weather control switch on for boiler circulation R Active return protection B Preset temperature increase to load the buffer 5 Symbol signalli...

Page 10: ...TEMPERATURE SETTING The preset boiler temperature and preset circuits temperature can be set in the menu possible temperatures are restricted with range of respective service parameters of the contro...

Page 11: ...lowing power which influence on actual boiler s power level Power levels parameters are available in the menu Menu Boiler settings Power modulation The controller regulates burner s power with which i...

Page 12: ...temperature gradually decreasing Incorrect settings can cause boiler overheating Maximum time of boiler s operating in supervision mode is defined in parameter Supervision time If after this time in S...

Page 13: ...flora It is absolutely important to inform all the inmates about activating the disinfection function There is a danger of scalding with HW hot water Once a week at night between Sunday and Monday at...

Page 14: ...value when preset temperature in a room will be reached Similarly like it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recom...

Page 15: ...nsulated require setting heating curve with higher values and for better isolated buildings heating curve will have lower value Preset temperature counted according to heating curve can be decreased o...

Page 16: ...Service settings Settings of CH and HW Settings of time control of circular pump are analogical to settings of night reductions In defined time periods circular pump is deactivated In omitted periods...

Page 17: ...r connecting additional B module the controller can cooperate with low fuel level sensor in silo After activating sensor for Auxiliary feeder operation time controller will connect auxiliary feeder to...

Page 18: ...18 USER MANUAL FOR INSTALLING THE CONTROLLER AND SERVICE SETTINGS R Control 890...

Page 19: ...ely it is necessary to isolate it thermally from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Page 20: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HW settings Activating operation buffer servic...

Page 21: ...active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer s...

Page 22: ...The controller can not be exposed to immediate effects of atmospheric conditions i e rain or sunrays Temperature of storage and transport should be within scope 15 65 degrees C During transport the c...

Page 23: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Page 24: ...is not acceptable to twist wires inside the device Wires inside the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling...

Page 25: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Page 26: ...n Wires of the sensors are resistant to temperature not exceeding 100 C 12 8 WEATHER SENSOR CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be installed on...

Page 27: ...STAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler operation select Thermostat selection f...

Page 28: ...rm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceeds preset value i e 25 degrees C then controller switches off additional boiler it will g...

Page 29: ...roller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes...

Page 30: ...rical power to mixer servomotor with the controller according to point 12 4 and value servomotor producer s documentation Do not confuse opening direction with closing direction Connect electrical pow...

Page 31: ...nsulation which is thick enough to meet safety standards of the boiler 12 18 ROOM PANEL CONNECTION It is possible to equip the controller with room panel ecoSTER200 which has following functions Room...

Page 32: ...me Cleaning blow Supervision Supervision time Feeding time Cycle time Blowing power Min blowing power Lack of fuel detection time Feeder max temperature Additional feeder operation time Boiler setting...

Page 33: ...in bakery The burner operates with maximum power without modulation of power The burner deactivates with disconnecting thermostat joints 28 29 Boiler temperature sensor does not influence feeder opera...

Page 34: ...3 failed attempts it reports alarm Failed firing up attempt Feeder max temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temperature Additional feed...

Page 35: ...e when HW loading Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parame...

Page 36: ...re below which buffer feeding starts Buffer feeding process is finished when low temperature reaches value defined in parameter Buffer feeding end temperature Stop feeding temperature 14 5 MIXER SERVI...

Page 37: ...xer setting activated FLOOR is also limit temperature of mixer sensor when mixer pump is deactivated For floor heating set the value below 45 degrees C 50 degrees C or other if producer of materials u...

Page 38: ...vanced Options available YES displays hidden parameters which edition is not recommended NO hides hidden parameters 15 Default settings restoring Default settings restore Restoring service settings Se...

Page 39: ...erature above service parameter MENU Service settings Burner settings Max feeder temperature If the feeder temperature increases above this value the controller will begin burning off procedure Alarm...

Page 40: ...rm reminder It will take place by failed attempt of feeding fuel from additional silo In case when through configured time of feeding the silo installed sensor not detects increase of fuel the reminde...

Page 41: ...n MENU Boiler settings Power modulation Boiler settings Power modulation 100 Blowing power 100 Feeder work 100 Oxygen 50 Hysteresis H2 50 Blowing power 50 Feeder work 50 Oxygen 30 Hysteresis H1 30 Blo...

Page 42: ...nd or twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional feeder is not working module B Check if feeder wires are correctly connec...

Page 43: ...ly made after closing the valve return temperature must increase above value of parameter Minimum return temperature The cause may be calibration of mixer valve wait until calibration is finished Acti...

Page 44: ......

Page 45: ......

Page 46: ......

Reviews: