BurnPell RControl EM890 User Manual Download Page 15

15 

 

 
 
For mixer cycle: 

Mixer settings 1 

 Mixer 

room thermostat

 = 0 

In 

case 

of 

connected 

room 

panel 

ecoSTER200 

set 

additionally 

room 

temperature factor

 = 0 

 

Guidelines for correct heating curve settings: 

Floor heating         0,2 – 0,6 

Radiator heating    1,0 – 1,6 

Buffer                  1,8 - 4  

 

Pic. 9 Heating curves. 

 
Tips for choosing proper heating curve: 
If  by  falling  outer  temperature  room 
temperature  is  increasing,  then  value  of 
chosen heating curve is too big, 
If  by  decreasing  outer  temperature,  room 
temperature is also decreasing, then value of 
chosen heating curve is too low, 
If  by  frosty  weather  room  temperature  is 
appropriate and in warmer time is too low – 
it  is  recommended  to  increase  parameter 

Heating  curve  parallel  shift

  and  then  choose 

lower heating curve, 
If by frosty weather room temperature is too 
low  and  in  warmer  time  too  high  –  it  is 
recommended  to  reduce 

Parameter  heating 

curve parallel shift

 and choose higher heating 

curve. 
 
Buildings  which  are  poorly  insulated  require 
setting heating curve with higher values, and 
for  better  isolated  buildings  heating  curve 
will have lower value. 

 
 

Preset  temperature,  counted  according  to 
heating curve can be decreased or increased 
by  controller  when  it  goes  beyond  scope  of 
limits of temperatures for given cycle. 

8.17. 

NIGHT 

REDUCTION 

SETTINGS 

DESCRIPTION 
In  the  controller  it  is  possible  to  set  time 
periods  of  silo  temperature  reduction, 
heating  cycles,  hot  water  silo,  and  circular 
pump.  
Time  periods  allow  setting  temperature 
reduction in given time period – i.e. at night 
or  when  user  leaves  the  heated  room. 
Thanks  to  it  preset  temperature  can  be 
reduced  automatically,  without  loss  of 
heating 

comfort 

by 

reducing 

fuel 

consumption.  
 
To activate time periods use parameter 

Night 

reduction

 

for  given  cycle  and  activate  it. 

Night reductions can be defined separately in 
working days, Saturdays and Sundays.  

 

Pic. 10 Window of time periods choosing. 

It is needed to set the beginning and the end 
of  given  time  period  and  value  with  which 
the preset temperature will be reduced.  

 

Pic. 11 Time periods edition. 

 
Below  sample  preset  night  temperature 
reduction is presented.  

Summary of Contents for RControl EM890

Page 1: ...unctions available in additional module B functions available in additional module MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 0 APPLIES FOR...

Page 2: ......

Page 3: ...ONDITIONS 22 12 CONTROLLER INSTALLATION 22 12 1 ENVIRONMENTAL CONDITIONS 22 12 2 INSTALLATION REQUIREMENTS 22 12 3 INSTALLATION 23 12 4 ELECTRIC CIRCUIT CONNECTION 23 12 5 SAFETY CONNECTIONS 24 12 6 E...

Page 4: ...4 17 4 NETWORK FUSE REPLACEMENT 40 17 5 CONTROL PANEL REPLACEMENT 40 18 LAMBDA PROBE 41 19 POSSIBLE FAULTS DESCRIPTION 42 20 CONTROLLER CONFIGURATION BY BOILER PRODUCER 43 21 CHANGES REGISTER 43...

Page 5: ...eder etc The controller is for boiler pellet burner producers The producer before its use should check if the cooperation between the controller and the boiler burner is correct and is not dangerous T...

Page 6: ...ser s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get acquai...

Page 7: ...USER MANUAL FOR CONTROLLER R Control 890...

Page 8: ...ion Automatic disinfection SUMMER Switch on temperature SUMMER Switch off temperature SUMMER Mixer settings 1 2 3 4 5 Mixer preset temperature Room mixer thermostat Mixer weather control Mixer heating...

Page 9: ...iler preset temperature increase from mixer circulation P Weather control switch on for boiler circulation R Active return protection B Preset temperature increase to load the buffer 5 Symbol signalli...

Page 10: ...TEMPERATURE SETTING The preset boiler temperature and preset circuits temperature can be set in the menu possible temperatures are restricted with range of respective service parameters of the contro...

Page 11: ...lowing power which influence on actual boiler s power level Power levels parameters are available in the menu Menu Boiler settings Power modulation The controller regulates burner s power with which i...

Page 12: ...temperature gradually decreasing Incorrect settings can cause boiler overheating Maximum time of boiler s operating in supervision mode is defined in parameter Supervision time If after this time in S...

Page 13: ...flora It is absolutely important to inform all the inmates about activating the disinfection function There is a danger of scalding with HW hot water Once a week at night between Sunday and Monday at...

Page 14: ...value when preset temperature in a room will be reached Similarly like it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recom...

Page 15: ...nsulated require setting heating curve with higher values and for better isolated buildings heating curve will have lower value Preset temperature counted according to heating curve can be decreased o...

Page 16: ...Service settings Settings of CH and HW Settings of time control of circular pump are analogical to settings of night reductions In defined time periods circular pump is deactivated In omitted periods...

Page 17: ...r connecting additional B module the controller can cooperate with low fuel level sensor in silo After activating sensor for Auxiliary feeder operation time controller will connect auxiliary feeder to...

Page 18: ...18 USER MANUAL FOR INSTALLING THE CONTROLLER AND SERVICE SETTINGS R Control 890...

Page 19: ...ely it is necessary to isolate it thermally from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Page 20: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HW settings Activating operation buffer servic...

Page 21: ...active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer s...

Page 22: ...The controller can not be exposed to immediate effects of atmospheric conditions i e rain or sunrays Temperature of storage and transport should be within scope 15 65 degrees C During transport the c...

Page 23: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Page 24: ...is not acceptable to twist wires inside the device Wires inside the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling...

Page 25: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Page 26: ...n Wires of the sensors are resistant to temperature not exceeding 100 C 12 8 WEATHER SENSOR CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be installed on...

Page 27: ...STAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler operation select Thermostat selection f...

Page 28: ...rm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceeds preset value i e 25 degrees C then controller switches off additional boiler it will g...

Page 29: ...roller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes...

Page 30: ...rical power to mixer servomotor with the controller according to point 12 4 and value servomotor producer s documentation Do not confuse opening direction with closing direction Connect electrical pow...

Page 31: ...nsulation which is thick enough to meet safety standards of the boiler 12 18 ROOM PANEL CONNECTION It is possible to equip the controller with room panel ecoSTER200 which has following functions Room...

Page 32: ...me Cleaning blow Supervision Supervision time Feeding time Cycle time Blowing power Min blowing power Lack of fuel detection time Feeder max temperature Additional feeder operation time Boiler setting...

Page 33: ...in bakery The burner operates with maximum power without modulation of power The burner deactivates with disconnecting thermostat joints 28 29 Boiler temperature sensor does not influence feeder opera...

Page 34: ...3 failed attempts it reports alarm Failed firing up attempt Feeder max temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temperature Additional feed...

Page 35: ...e when HW loading Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parame...

Page 36: ...re below which buffer feeding starts Buffer feeding process is finished when low temperature reaches value defined in parameter Buffer feeding end temperature Stop feeding temperature 14 5 MIXER SERVI...

Page 37: ...xer setting activated FLOOR is also limit temperature of mixer sensor when mixer pump is deactivated For floor heating set the value below 45 degrees C 50 degrees C or other if producer of materials u...

Page 38: ...vanced Options available YES displays hidden parameters which edition is not recommended NO hides hidden parameters 15 Default settings restoring Default settings restore Restoring service settings Se...

Page 39: ...erature above service parameter MENU Service settings Burner settings Max feeder temperature If the feeder temperature increases above this value the controller will begin burning off procedure Alarm...

Page 40: ...rm reminder It will take place by failed attempt of feeding fuel from additional silo In case when through configured time of feeding the silo installed sensor not detects increase of fuel the reminde...

Page 41: ...n MENU Boiler settings Power modulation Boiler settings Power modulation 100 Blowing power 100 Feeder work 100 Oxygen 50 Hysteresis H2 50 Blowing power 50 Feeder work 50 Oxygen 30 Hysteresis H1 30 Blo...

Page 42: ...nd or twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional feeder is not working module B Check if feeder wires are correctly connec...

Page 43: ...ly made after closing the valve return temperature must increase above value of parameter Minimum return temperature The cause may be calibration of mixer valve wait until calibration is finished Acti...

Page 44: ......

Page 45: ......

Page 46: ......

Reviews: