13
Figure 5B: Top View - Burner Swing Door Mounted to Cast Iron Block Assembly (Jacket Removed for Clarity)
By design, door insulation on model MST629
will
have
two by-pass pockets cast into the insulation
centered on the bar between the combustion
chamber and 3rd pass flueways. By design, door
insulation on models MST288, MST396 & MST513
will not have
any by-pass pockets. If insulation is
damaged, or, improper type regarding the pockets, it
must be replaced.
11. Upon inspection completion, lift door and place
integral cast hinge pins into door mounting bracket
slotted holes. Do not close and secure door at this
time, proceed to installing stainless steel flueway
baffles.
12. Locate/remove four #8 x ½” shoulder sheet metal
screws from Hardware Bag, then, install them into
front panel flange holes.
Summary of Contents for MST288
Page 11: ...11 Figure 4 Boiler Removal from Skid ...
Page 19: ...19 Figure 9 Float Type LWCO and Pressure Limit Installation ...
Page 25: ...25 Figure 12 Recommended Boiler Piping for Gravity Return Steam Boiler ...
Page 34: ...34 Figure 18 Wiring Diagram Steam Hydrolevel CG450 Probe LWCO ...
Page 35: ...35 Figure 18A Wiring Diagram Riello 40 Series Burner Steam Hydrolevel CG450 Probe LWCO ...
Page 36: ...36 Figure 19 Wiring Diagram Steam McDonnell Miller PS 801 Probe LWCO ...
Page 37: ...37 Figure 19A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller PS 801 Probe LWCO ...
Page 38: ...38 Figure 20 Wiring Diagram Steam McDonnell Miller 67 Float LWCO ...
Page 39: ...39 Figure 20A Wiring Diagram Riello 40 Series Burner Steam McDonnell Miller 67 Float LWCO ...
Page 45: ...45 Figure 24 L1 and V1 Head Electrode Positioning and Gun Setting Beckett AFG ...
Page 58: ...58 Bare Boiler Assembly ...
Page 60: ...60 Jacket Assembly ...
Page 62: ...62 MST288 Thru MST629 Steam Boilers Trim and Controls ...
Page 64: ...64 Beckett AFG Burner ...