70
107672-03 - 5/18
IX. System Piping
(continued)
2. Gauge (Required) - Indicates supply water pressure and temperature. This gauge is shipped loose.
Install it as shown in Figure 9.9.
3. Circulator (required) – The boiler loop circulator is factory installed inside the boiler cabinet. Usually
at least one addition circulator (not supplied) will be required for the system to work properly. See the
previous section for more information.
4. Expansion Tank (required) – If this boiler is replacing an existing boiler with no other changes in the
system, the old expansion tank can generally be reused. If the expansion tank must be replaced,
consult the expansion tank manufacturer’s literature for proper sizing. If using antifreeze, account for
additional expansion of glycol solution when sizing an expansion tank. In a typical residential heating
system, a glycol mixture has an expansion rate about 1.2 times that of water alone, therefore a tank for
an anti-freeze system should be at least 1.2 times greater in size.
5. Fill Valve (required) – Either a manual or automatic fill valve may be used, but a manual valve is preferred
because it eliminates unmonitored additions of make-up water to the system. The ideal location for the
fill valve is at the expansion tank. If using antifreeze with automatic fill valve, it is recommended to install
a water meter to monitor makeup water. Antifreeze concentration will decrease as makeup water is
added. If using antifreeze, local codes often require a backflow preventer or disconnect from city water.
6. Automatic Air Vent (required) – At least one automatic air vent is required. Manual air vents will usually
be required in other parts of the system to remove air during initial fill.
7. Manual Reset High Limit (required by some codes) - This control is required by ASME CSD-1 and some
other codes. Install the high limit in the boiler supply piping just above the boiler with no intervening
valves. Set the manual reset high limit to 200°F. Wire the limit per Figure 10.3 in the Wiring section.
8. Isolation Valves (recommended) - Isolation valves are useful when the boiler must be drained, as they
will eliminate having to drain and refill the entire system.
9. Strainer (recommended) – Install a Y Strainer, or other suitable strainer, to prevent any system debris
from entering the boiler and fouling the water passages. Note that some strainers have a significant
pressure drop, which may impact the ability of the boiler pump to obtain the required flow. See
Paragraph B of this section for additional information.
B. Standard Piping Installation Requirements
Observe the following requirements when installing the boiler piping:
1. Relief Valve (Required) – The relief valve is shipped loose and must be installed in the location shown
in Figure 9.9, using the side outlet Tee and other fittings provided. ASME Section IV currently requires
that this relief water or stream will not create a hazard or cause property damage if the valve opens. The
end of the discharge pipe must terminate in unthreaded pipe. If the relief valve discharge is not piped
to a drain, it must terminate at least 6” above the floor. Do not run the discharge piping through an area
that is prone to freezing. The termination of the relief valve must be in an area where it is not likely to
become plugged by debris.
The relief valve supplied with the boiler is set to open at 30 psi. If it is replaced, the replacement must
have a setting less than or equal to the maximum allowable working pressure (MAWP) shown on the
ASME data plate located on the left side of the heat exchanger behind the service access panel (Figure
9.9).
Explosion / Scald Hazard. Pipe relief valve discharge to a location where the potential
of severe burns is eliminated.
Do not install a relief valve having a setting greater than the MAWP shown on the rating plate.
Do not install a valve in the relief valve discharge line.
Do not install relief valve in a location other than that specified by the factory.
Do not plug the relief valve discharge.
Do not install a valve between boiler and boiler relief valve.
DANGER
•
•
•
•
•
Summary of Contents for K2WT Residential
Page 88: ...88 107672 03 5 18 X Wiring continued Figure 10 7 Internal Ladder Diagram ...
Page 89: ...89 107672 03 5 18 PAGE LEFT INTENTIONALLY BLANK ...
Page 90: ...90 107672 03 5 18 X Wiring continued ...
Page 91: ...91 107672 03 5 18 Figure 10 8 Internal Wiring Connections Diagram X Wiring continued ...
Page 103: ...103 107672 03 5 18 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Page 148: ...148 107672 03 5 18 XV Service Parts continued ...
Page 152: ...152 107672 03 5 18 XV Service Parts continued ...
Page 154: ...154 107672 03 5 18 XV Service Parts continued 85 86 91 95 ...
Page 163: ...163 107672 03 5 18 ...
Page 164: ...164 107672 03 5 18 ...
Page 165: ...165 107672 03 5 18 ...
Page 166: ...166 107672 03 5 18 ...
Page 167: ...167 107672 03 5 18 ...