
50
d) Remove the ignition electrode and inspect it for oxides. Clean the oxides off the electrode with
sandpaper. Inspect the ceramic insulator for cracks and replace the ignitor assembly as necessary.
e) Remove any accumulated debris from the air inlet screen.
f) Remove the attenuator hose and clean as necessary. (Note: The nylon cable tie used to hold the
attenuator hose in place is releasable.)
g) Remove the combustion fan/gas valve assembly and inspect the fan and fan blade for lint and dust.
Vacuum as required.
h) Remove the burner hood to access the burner and the chamber.
i) Check the burner and clean off any foreign material that may have accumulated. This can be done by
dusting with a soft bristle type brush or a vacuum cleaner. DO NOT USE A WIRE BRUSH TO CLEAN
THE BURNER. Check for corrosion of the burner and its parts. If there is evidence of corrosion or
deterioration, replace immediately.
j) With the burner removed, inspect the combustion chamber and clean as necessary.
k) Clean heat exchanger. Use vacuum to remove accumulation of any loose particulate from the pins and
heat transfer surfaces. Clean the casting pins by flushing with clean water using a standard garden spray
nozzle. Do not use any cleaning agents or solvents.
A soft nylon brush
may be used in accessible area.
Remove inspection cover and inspect Condensate collector sump. Drain and flush the condense collector
and condensate drain as required.
l) Do not use any cleaning agents or solvents.
m) Inspect the condensate trap to verify it is open and free from debris. Clean if necessary.
n) Reinstall the burner, burner hood, combustion fan, gas valve assembly and the attenuator hose.
o) Reconnect any wiring which has been disconnected.
p) Qualified service personnel should thoroughly inspect the heating system and correct any deficiencies
prior to restarting the boiler.
q) Follow Section xI Start-up and Checkout instructions before leaving installation.
r) Perform the combustion test outlined in Section xI.
s) Ensure system water is within required PH range (6.0 and 8.5).
t) Inspect vent system.
• To ensure all joints and pipe connections are tight.
• To ensure it is free from debris, cracks, corrosion and/or deterioration. If any piping needs replacing,
do so immediately.
Summary of Contents for CHG CHG150
Page 25: ...25 Figure 8 3 Piping Method 1 Heat Indirect Water Heater Figure 8 2 Piping Method 1 Heat Only ...
Page 29: ...29 Figure 8 8 Piping Method 2 Heat Only Figure 8 9 Piping Method 2 Heat Indirect Water Heater ...
Page 36: ...36 Figure 9 1 Wiring Connections Diagram ...
Page 37: ...37 Figure 9 2 Ladder Diagram ...
Page 38: ...38 Figure 9 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 40: ...40 CHG Series Lighting and Operating Instructions ...
Page 46: ...46 Figure 11 2 Basic Menu Tree ...
Page 54: ...54 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...
Page 63: ...63 ...
Page 65: ...65 ...
Page 66: ...66 ...
Page 67: ...67 ...
Page 69: ...69 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 70: ...70 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 71: ...71 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 72: ...9EARS IN 3ERVICE 3ERVICE HARGE AS OF 2ETAIL 0RICE O HARGE ...