19
Installationandwiring
Type 8228
8.4.2 making the installation equipotential
To ensure the equipotentiality of the installation (power supply -
device - medium):
→
Connect together the various earth spots in the installation to
eliminate the potential differences that may occur between dif-
ferent earthes.
→
Observe faultless earthing of the shield of the power supply
cable, at both ends.
→
If the device is installed on plastic pipes, earth together the
metallic instruments such as pumps or valves, that are as close
as possible to the device.
12-36 V DC
+
-
Power supply
Metal pipe
Fig. 10: Equipotentiality skeleton diagram with pipes in metal
Devices such as valves, pumps,...
12-36 V DC
+
-
Power supply
Plastic pipe
Fig. 11: Equipotentiality skeleton diagram with pipes in plastic
English
Summary of Contents for 8228 ELEMENT
Page 32: ...www burkert com ...