16
Installationandwiring
Type 8228
8.2 installing a 8228 with a G2'' process
connection in the pipe
The device is put into a fitting Type S020 mounted on the pipe.
→
Mount the fitting on the pipe obeying the instructions of the
Operating Instructions of the fitting used.
Fig. 5:
Positions for the mounting on the pipe
Tank without mixing
device
Tank with mixing device
Fig. 6:
Positions for the mounting on a tank
→
Fit the display module (see chap. 7.2) to calibrate the conduc-
tivity sensor and to parameter the device.
→
Calibrate the zero point of conductivity (see chap. 9.7).
→
Install the device in the fitting as shown in Fig. 7:
1
2
3
4
5
→
Make sure the seal (mark 2) is on
the conductivity sensor.
→
Make sure the material of the seal
is compatible with the fluid to be
measured.
→
Put the nut (mark 5) on the fitting.
→
Put the snap ring (mark 3) into the
groove (mark 4).
→
Engage the device (mark 1) into
the fitting.
→
Screw the nut (mark 5) manually
on the device.
Fig. 7:
Installation of a 8228 with G2'' process connection into the S020
fitting
→
Wire according to instructions in chap. 8.4.
English