4.3.4 Output 1 (Base)
Select the controller output 1 logic signal.
Impulse time selection (PULSE 1)
Set the duration of each impulse and the maximum frequency of the output signal.
Impulse frequency selection (PWM1)
Set the frequency of the logic output signal activation.
OUTPUT 1
OUTPUT 2
PWM 1
T1
=
000,0S
OUTPUT 2
000 / MIN
012 / MIN
T1
=
012,3S
T1
=
000,0S
T1
=
001,5S
(T1 (s)+0,02 (s)) x F1 < 60
Internal checking of this condition
is provided. If this is not, the
program returns to T1 selection
until complying with the required
condition.
Impulse
Duration
(T1)
Impulse
Frequency
(F1)
Impulse
Duration
(T1)
PULSE 1
4 OPERATION
!
If the pulse output is provided by a relay; set F1 < 60. (cf § 2.5)