33
Electrical connection
10.4
Electrical installation, IO-Link
M8 socket, 4-pin
(remote variant only)
M12 plug x 1, 5-pin
1
2
3
4
5
4
2
1
3
Fig. 23: Pin assignment
Pin assignment port class A
Pin
Designation
Assignment
1
L +
24 V DC
System supply
2
I/Q
NC
Not used
3
L –
0 V (GND)
System supply
4
C/Q
IO-Link
Communication
5
NC
NC
Not used
Tab. 22: Pin assignment port class A
Pin assignment port class B
Pin
Designation
Assignment
1
L +
24 V DC
System supply
2
P24
24 V DC
Actuator supply
3
L –
0 V (GND)
System supply
4
C/Q
IO-Link
Communication
5
N24
0 V (GND)
Actuator supply
Tab. 23: Pin assignment port class B
You can find the pin assignment of the remote variant in
the chapter “10.6”
10.5
Electrical installation, büS
M8 socket, 4-pin
(remote variant only)
M12 plug x 1, 5-pin
1
2
3
4
5
4
2
1
3
Fig. 24: Pin assignment
Pin
Wire colour
Assignment
1
CAN label/shielding
CAN label/shielding
2
red
24 V DC ±25%
max. residual ripple 10%
3
black
GND/CAN_GND
4
white
CAN_H
5
blue
CAN_L
Tab. 24: Pin assignment
For electrical installation with büS network note the
following:
Use a 5-pin circular plug and a shielded 5-wire cable.
The shielding is capacitively connected to the functional
earth through the device.
Type 8791 REV.2
english
Summary of Contents for 323219
Page 40: ......