ELECTRICAL REQUIREMENTS - U3, U3A, U333, U38, U3833
CAUTION -
The brewer must be disconnected from the power source until specified in Initial Set-Up.
U333 & U3833
requires 3-wire, grounded service
rated 240 volt ac, 35 amp or 440 volts ac, 30 amp
for U333,three phase, 60 Hz or 380 volts ac, 30 amp
for U3833, three phase, 50 Hz.
U3 & U38
requires 3-wire, grounded service rated
120/208 or 120/240 volts ac, U3/SRU-30 amp,U38-40
amp, single phase, 60 Hz.
U3A
models require 2-wire, grounded service rated
230 volts ac, 30 amp, single phase, 50 Hz.
U3833
requires 4-wire, grounded service rated 380
volts ac or 440 volts ac, 30 amp, three phase, 50 Hz.
GREEN
GREEN
L1, L2, L3, are the 3 phases
V1 = Phase to phase voltage,
between any 2 phases.
V2 = Phase to neutral voltage,
any phase to neutral.
SYSTEM
VOLTAGE
V1
V2
208
208 120
240
240 139
380
380 220
440
440 254
P1842
P1844
42769 041910
GREEN
GREEN
L2 RED
WHITE
NEUTRAL
L1 BLACK
120V A.C.
208 OR
240V A.C.
RED
BLACK
BLUE
120V A.C.
208V OR 240V
380V OR 440V
208V OR 240V
380V OR 440V
208V OR 240V
380V OR 440V
P1841
P1843
L2
L3
L1
RED
BLACK
L1
L2
L3
N
WHITE
BLUE
(NEUTRAL)
U3A
Requires 2-wire, gorunded service rated 230
volts ac, 32 Amps, single phase, 50 Hz.
FACTORY WIRED
U3A
Requires 4-wire, 3-phase grounded service
rated 400 volts ac, 15 amp, 3 phase, 50 Hz.
FIELD WIRING
RED
BLACK
L1
L2
230V A.C.
ELECTRICAL REQUIREMENTS - U3A (UK)
CAUTION -
The brewer must be disconnected from the power source until specified in Initial Set-Up.