Vertical SpaceKeeper – Installation Operation Maintenance Manual
6
© Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice- Last Revised Oct 1, 2014
LOCATION
1.
Determine floor mount location with clearances
as shown in Table 1 on page 3.
2.
Locate the unit in an indoor area. The ambient
temperature surrounding the unit must not be
less than 45°F (7C°). Do not locate the unit in
areas subject to freezing.
PLACEMENT
1.
Position the unit ensuring the unit is level.
2.
Meet specified clearances to provide room for
removal of all access panels
(see Table 1 for details).
3.
Provide access to water shut off valves and
fittings. Provide screwdriver access to the unit
side panels, discharge collar, and all electrical
connections.
PIPING
CAUTION: Piping must comply with all applicable
codes.
1.
Install shut off valves at each unit to permit unit
removal.
2.
DO NOT bend or kink supply lines or hoses (if
supplied). Supply and return hoses (available
from factory) are fitted with swivel joint fittings
at one end to allow removal for future
servicing.
3.
The SpaceKeeper Vertical units are internally
trapped. Do not install another trap on the
condensate pipe that leaves the SpaceKeeper
unit.
Figure 2