TC-Double (+) X2
Connection via plug
The device is equipped with connectors according to EN 175301-803 for mains and status output. If the cables are mounted prop-
erly, they cannot be interchanged. Please make sure that the connectors are remounted correctly after connecting the cable. The
following figures show the pin assignment with respect to the numbers printed on the connector.
The supply line cross-sections must be suitable for the rated current. Use a maximum line cross-section of 1.5 mm² (AWG 16) and
a cable diameter of 8 - 10 mm (0.31 - 0.39 inch).
Plug numbering
Electric supply S1
Alarm contact S2
Analogue output S3
1 - N/C
2 - N/C
3 - GND
4 - 4-20 mA out
5 - shield
*
*
* When using an alarm contact connect to ≥ 33 V AC or ≥ 70 V DC PE voltage.
The clamping areas for S1 and S2 are 8 - 10 mm (0.31 – 0.39 inch) in diameter.
4.4 Signal outputs
The device has various status signals. The maximum switching power of the alarm outputs is 250 V AC/150 V DC, 2 A, 50 VA,
each.
An alarm is triggered by the alarm contact / status output (S2) if the temperature in block 1 is outside the specified limits. It does
not indicate if the alarm was triggered due to excess temperature or insufficient temperature.
Description of signal outputs
Function / contact type
Description
Regard-
ing S2)
internal changeover con-
tact: max. 250 V AC /
150 V DC, 2 A, 50 VA
the following device statuses
can be indicated via two
switching outputs:
Contact between 3 and 2 closed (alarm)
– No mains voltage and/or actual temperature outside
the alarm thresholds
Contact between 3 and 1 closed (ok)
– Mains voltage at actual temperature within the
alarm thresholds
With temperature signal option
Regard-
ing S3)
4-20 mA analogue output
(R
Load
<500 Ω)
Signalling of actual temper-
ature in block 1 (please use
shielded cables)
T
Cooler
= -20 °C
≙
(-4 °F) -> 4 mA/ 2V
T
Cooler
= 5 °C
≙
(41 °F) -> 9 mA/ 4,5 V
T
Cooler
= 60 °C
≙
(140 °F) -> 20 mA/ 10 V
The front film on the display module has three LEDs:
Colour
Marking
Function
Red
S2
High/low temperature
Device error
Yellow
S1
Reserved
Green
OP
Normal operation
The LEDs OP and S2 indicate the device status similar to S2.
14
Bühler Technologies GmbH
BE440022 ◦ 10/2018