2
Product Information
SM80/5, SM100/5 – 6 720 800 156 (2017/07)
6
2.5
Pressure drop curve of heating coil
Pressure drop curve of bottom heat exchanger
Fig. 3
Pressure drop curve of bottom heat exchanger
[1]
SM80/5
[2]
SM100/5
Example:
[A]
8 gpm, 2.2feed of head
Pressure drop curve of top heat exchanger
Fig. 4
Pressure drop curve of top heat exchanger
[1]
SM80/5
[2]
SM100/5
Example:
[B]
8 gpm, 1.4 feed of head
20.00
feed of
head
gpm
15.00
10.00
5.00
0.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
6 720 800 155-18.2T
1
2
A
18.00
20.00
22.00
24.00
26.00
28.00
fee
d
o
f h
ead
If the two heat exchangers are piped in series, the
pressure drops are cumulative.
If they are operated in parallel, a separate pump is
recommended for each heat exchanger. Otherwise, flow
setters are needed to regulate the flow through the two
heat exchangers.
Ensure that in any case the pumps meet the load.
6 720 800 155-19.2T
20.00
feed of
head
gpm
15.00
10.00
5.00
0.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
1
2
B
18.00
20.00
22.00
24.00
26.00
28.00
feed o
f head