Maintenance
12
11.
Verify proper operation of the aquastat (Fig. 39,
Item. 10
).
12.
Test low water cut-off operation, if present.
13.
Check boiler surroundings for irregularities. Its
surroundings must be free of flammable materials,
gasoline or other flammable or corrosive gases and
liquids.
14.
Confirm the maintenance record by filling out all
listed items. Sign the maintenance record and hand
it to the owner/operator of the boiler.