20.1 Troubleshooting "NO HEAT" call
“BRENNER” (burner) wiring block
–
Terminal 4 – 120V Neutral
–
Terminal 8 – 120V input clocks hours run
meter (must be field wired)
–
Terminal 9 – 120V input displays “BURNER ERR”
message (must be field wired)
–
Terminal 10 / 11 – “dry” contacts close to energize
burner
–
Terminal 12 – 120V power (drops out when manual
reset limit is tripped)
Burner operation
The R2107 is not a cold start control. It does not reply on
a call for heat from an end switch or thermostat to fire the
boiler.
The boiler will maintain a range of water temperature
based on outdoor temperature. The differential of this
range is dynamic,
meaning that it is not fixed, and will adjust based
on outdoor temperature and current system load.
The starting point of the differential
is 27°F (15°C) and will adjust from there. The
differential will generally be wider at milder outdoor
temperatures and narrower at
colder outdoor temperatures. The differential is split
above & below the current target temperature.
Example: Outdoor temperature at 32°F, based on
heating curve the water temperature required is 140°F
with a 26°F burner differential.
The differential (26°F) is split (13°F) above & (13°F)
below the target temperature.
140°F 13°F = 153° high limit
140°F target - 13°F = 127° low limit
This 127°F to 153°F becomes the range of temperature
that the boiler will maintain. As zones call and pull heat
from the boiler, eventually the temperature in the boiler
drops. Once the temperature in the boiler hits the low
limit (127°F) the R2107 control closes a switch (dry
contacts) between terminals 10 & 11 to fire the boiler
(this is indicated by a flame symbol
displayed on
the LDC screen of the R2107). When the boiler
temperature reaches the high limit (153°F), the contacts
open and the boiler stops firing.
Once the outdoor temperature drops below the WWSD
setting, the boiler begins to maintain temperature.
Above WWSD the boiler will only fire on a call for DHW.