9
Solar data
9.1
Solar function ON/OFF
(with FM 244 only)
The Solar function menu option is used to optimize the solar gain and minimize
the use of fossil fuel.
To achieve this, the controllers for the solar heating system and the conventional
heating boiler are combined in a single unit. The controls monitors the current
solar gain and the stored heat in the DHW tank, and reduces the setpoint
temperature in the standby part of the DHW tank to prevent it being reheated
unnecessarily.
Switching off the solar function
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until the "SOLAR" main menu appears.
Press "Display" to call up a submenu.
"SOLAR ON" appears.
+
Hold down the "Display" key and turn the dial until the required value appears
(in this case "SLRFN OFF").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
SLRFN ON
SLRFN OFF
Input range
Factory setting
SOLAR
ON
OFF
ON
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
4
3
9
S
olar data