8.6
Maximum room temperature
compensation
The room temperature compensation adjusts the calculated outdoor reset
heating curve according to the measured room temperature.
Any deviations from the room setpoint are then corrected immediately by
adjusting the boiler setpoint temperature accordingly.
The maximum differential temperature can only be entered if the remote control
has been activated. The influence of the room temperature on the DHW
temperature (heating curve) is thus limited.
The factory setting is:
Further information on this can be found on the next page.
USER NOTE
The maximum room temperature hook-up determines the range within which
deviations from the room setpoint value may be corrected. Influencing factors
such as open windows or additional heat sources, e.g. wood burning stove,
open fireplace, are thus eliminated in the area where the remote control is
installed. If other rooms are supplied with heat via this heating circuit, then the
aforementioned influencing factors can cause these near-by rooms to be
supplied with insufficient heat. The function should be set to "OFF" to eliminate
the chance of insufficient supply.
USER NOTE
If you entered "OFF", the room temperature no longer has any influence on the
supply temperature (heating curve).
This setting is generally recommended for FLOOR HTG systems.
With FLOOR HTG system:
6°F (3°C)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
3
8
5
4