Inspection and maintenance
Logalux – 6721829955 (2020/12)
48
9.4
Maintenance work
9.4.1
Testing the pressure relief valve
▶ Check the pressure relief valve annually.
9.4.2
Descaling and cleaning
In order to improve the cleaning effect, heat up the heat exchanger prior
to cleaning it with a water jet. The thermal shock effect separates
deposits (e.g. limescale) more readily.
▶ Isolate the cylinder from the piping on the domestic water side.
▶ Close the shut-off valves and isolate the immersion heater (if used)
from the mains power supply. (
▶ Drain the cylinder (
▶ Open the inspection aperture on the cylinder.
▶ Check the interior of the cylinder for pollution.
-or-
▶
In the case of soft water:
Check the container regularly and clean to remove limescale.
-or-
▶
In the case of hard water or severe pollution:
Regularly descale the cylinder in line with the actual amount of
limescale using chemical cleaning methods (e.g. with a suitable
descaling agent based on citric acid).
▶ Hose down the inside of the cylinder (
▶ Use a wet & dry vacuum cleaner with plastic suction hose to remove
the residues.
▶ Close the inspection aperture with a new gasket
(
9.4.3
Checking the magnesium anode
Failure to service the magnesium anode properly voids the warranty for
the cylinder.
The magnesium anode is a sacrificial anode, which is consumed when
the cylinder is in operation. Two types of magnesium anode can be used.
• A non-insulated magnesium anode (
• An insulated magnesium anode (
Variant B, Fig. 26, page 74).
We recommend that insulated magnesium anodes are additionally
checked regarding the protection current using an anode tester on an
annual basis (
Fig. 24, page 74). The anode tester is available as an
accessory.
NOTICE
Corrosion damage!
If the anode is neglected, this could lead to premature corrosion.
▶ Inspect the anode every one or two years, depending on the on-site
water quality, replace if required.
Never bring the magnesium anode surface into contact with oil or grease.
▶ Keep everything clean.
▶ Shut off the cold water inlet.
▶ Depressurise the cylinder (
▶ Remove and test the magnesium anode
(
▶ Replace the magnesium anode if its diameter has been reduced to
less than 15 mm.
▶ If the magnesium anode is insulated: check the transfer resistance
between the protective conductor connection and the magnesium
anode. If the anode current is <0.3 mA, replace the magnesium
anode (
Fig. 24, page 74).
9.4.4
Recommissioning
▶ Flush the cylinder thoroughly after cleaning or repair.
▶ Vent on the heating side and on the domestic water side.
9.5
Function check
NOTICE
Damage through positive pressure.
A pressure-relief valve malfunction can result in damage due to positive
pressure.
▶ Check the pressure-relief valve function and flush through several
times by venting.
▶ Never close the blow-off opening of the pressure-relief valve.
9.6
Checklist for maintenance
▶ Fill out the report and note the tasks performed.
Table 54 Checklist for inspection and maintenance
Date
1
Check the function of the
pressure-relief valve
2
Check tightness of
connections
3
Descale/clean
the inside of the cylinder
4
Signature
Stamp
Summary of Contents for Logalux SM310.5 E
Page 38: ...6 Logalux 6721829955 2020 12 38 6 6 1 10 bar 6 2 6 2 60 C 44 44 7 16 17 72 18 72 19 72 8 Bosch...
Page 66: ...Logalux 6721829955 2020 12 66 1 0010036157 001 1 10 11 12 13 14 15 16 17 4 7 8 9 2 3 5 6...
Page 69: ...Logalux 6721829955 2020 12 69 5 6 7 8...
Page 70: ...Logalux 6721829955 2020 12 70 9 10 11 0010036175 001 T 9 1 6 8 2 5 3 7 p1 p2 p1 p2 DN20 10 bar...
Page 73: ...Logalux 6721829955 2020 12 73 20 21 22 23 0010009742 001 25 30 Nm 19 22 ft lbs...
Page 75: ...Logalux 6721829955 2020 12 75 27 28 0010032899 001 1 1 2 3 0010032900 001...
Page 76: ...Bosch Thermotechnik GmbH Sophienstrasse 30 32 D 35576 Wetzlar www bosch thermotechnology com...